Bryant 581C Manual De Usuario

Descargar
Página de 298
152
PERFORMANCE DATA — 581C
COOLING CAPACITIES — 581C024-060 STANDARD UNITS (cont)
LEGEND
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:  
Where: h
ewb
= Enthalpy of air entering evaporator coil.
3. The SHC is based on 80 F edb temperature of air entering evapo-
rator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
581C048 (4 Tons)
Temp (F)
Air Entering Evaporator -- CFM/BF
Air Ent
1200/0.05
1600/0.07
2000/0.09
Condenser
Air Entering Evaporator -- Ewb (F)
(Edb)
62
67
72
62
67
72
62
67
72
75
TCG
46.3
51.1
55.7
48.8
53.5
58
50.7
54.9
59.1
SHG
39.9
33.8
27.1
46.3
38.6
29.8
50.6
42.7
32
CMP
2.36
2.37
2.38
2.37
2.38
2.39
2.37
2.38
2.39
85
TCG
42.9
49
54
46.2
51.5
56.4
49.2
52.8
57.4
SHG
38.5
33
26.6
45.2
37.9
29.4
49.1
42.2
31.7
CMP
2.69
2.71
2.72
2.71
2.72
2.74
2.72
2.72
2.74
95
TCG
38.7
45.8
51.9
42.6
48.8
54.2
46.8
50.4
55.5
SHG
36.5
31.8
25.9
42.5
37.1
28.9
46.8
41.6
31.4
CMP
3.05
3.08
3.11
3.07
3.1
3.12
3.1
3.11
3.12
105
TCG
34.4
41.1
49.1
39
43.8
51.5
43.3
46.3
52.8
SHG
34.3
30
24.9
39
35.3
28.2
43.3
40.4
30.9
CMP
3.42
3.48
3.53
3.47
3.5
3.54
3.5
3.52
3.54
115
TCG
31.4
36.3
44.7
35.8
38.4
47.3
39.2
40.6
49.5
SHG
31.4
28.1
23.5
35.8
33.3
26.9
39.2
38.1
30.1
CMP
3.85
3.9
3.96
3.9
3.92
3.98
3.93
3.94
4
125
TCG
28.2
31.1
39.8
31.9
33
41.6
35.3
35.4
43.9
SHG
28.1
26.2
21.8
31.9
31.1
25.1
35.3
35.4
28.4
CMP
4.31
4.35
4.42
4.36
4.37
4.44
4.4
4.4
4.46
581C060 (5 Tons)
Temp (F)
Indoor Entering Air -- CFM/BF
Outdoor
1500/0.26
1750/.31
2000/.35
2500/.45
Air Ent
Indoor Entering Air -- Ewb (F)
(Edb)
57
62
67
72
57
62
67
72
57
62
67
72
57
62
67
72
75
TCG 
57
60.2
66.5
72
60.3
62.3
68.5
73.8
63.2
64.1
69.7
75.6
67.4
67.4
71.8
77.6
SHG  55.3
50.5
42.4
33.5
58.6
55.2
45.7
35.4
61.3
59.5
48.6
37.4
65.5
65.5
54.4
40.7
CMP 
3.1
3.11
3.12
3.14
3.11
3.12
3.13
3.15
3.11
3.12
3.13
3.16
3.12
3.12
3.14
3.17
85
TCG  54.1
56.9
64
70.2
58.3
59.7
65.9
72
60.9
61.4
67.3
73.4
65.3
65.2
69.6
75.3
SHG  52.6
49.1
41.4
33
56.6
54.1
44.8
35
59.2
58.4
48
36.9
63.4
63.4
54.4
40.4
CMP 
3.5
3.52
3.54
3.56
3.52
3.53
3.54
3.57
3.53
3.54
3.54
3.58
3.54
3.54
3.56
3.59
95
TCG  50.2
53
61.1
67.5
55
55.6
62.9
69.3
58.6
58.6
64.3
70.6
62.8
62.8
66.4
72.7
SHG  48.8
47.4
40.3
32.2
53.4
52.3
43.8
34.2
56.9
56.8
47.2
36.1
61
61
53.4
40
CMP  3.94
3.95
3.99
4.02
3.97
3.97
4.01
4.03
3.99
3.99
4.02
4.03
4.01
4.01
4.02
4.05
105
TCG  47.4
47.9
56.5
64.3
50.9
51
59.5
66.1
54.7
54.8
60.9
67.4
59.9
60
62.9
69
SHG 
46
45.2
38.7
31.1
49.5
49.5
42.6
33.2
53.1
53.2
45.9
35.2
58.2
58.3
52.4
38.8
CMP  4.42
4.42
4.48
4.51
4.44
4.44
4.5
4.53
4.47
4.47
4.51
4.54
4.5
4.5
4.52
4.54
115
TCG  43.1
43.2
50.3
60.8
47.3
47.3
52.6
62.6
50.1
50.1
55.6
63.9
56
55.9
58.2
65.4
SHG  41.8
42
36.4
30
45.9
45.9
40.2
32.1
48.7
48.7
44.1
34.2
54.4
54.3
50.8
37.9
CMP  4.92
4.92
4.98
5.05
4.96
4.96
5
5.07
4.98
4.98
5.02
5.08
5.03
5.03
5.05
5.08
125
TCG 
39
39
43.9
55.7
42.3
42.3
46.9
58.5
46.1
46.1
48.2
59.7
50.9
50.9
51.3
61.4
SHG  37.9
37.9
34.1
28.3
41.1
41
38.2
30.8
44.8
44.8
41.6
32.9
49.4
49.4
48.2
36.9
CMP  5.47
5.46
5.52
5.62
5.51
5.51
5.55
5.64
5.54
5.54
5.56
5.66
5.59
5.59
5.59
5.66
BF
— Bypass Factor
Edb
— Entering Dry Bulb
Ewb
— Entering Wet Bulb
COMP —  Compressor Power  kw
SHG
— Gross Sensible Capacity (1000 Btuh) 
TCG
— Compressor Cooling Capicity  (1000 Btuh)
t
ldb
=
t
edb
sensible capacity (Btuh)
1.10 x cfm
t
lwb
= Wet-bulb temperature corresponding to enthalpy of air 
leaving evaporator coil (h
lwb
)
h
lwb
= h
ewb
total capacity (Btuh)
4.5 x cfm
58
1C02
4-
060