PERFORMANCE DATA — 579F (cont)
EVAPORATOR-FAN MOTOR DATA
LEGEND
*Extensive motor and electrical testing on these units ensures that the full horsepower (brake kilowatt) range
of the motors can be utilized with confidence. Using fan motors up to the horsepower (brake kilowatt) ratings
shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be
affected.
NOTE: All indoor-fan motors 5 hp and larger meet the minimum efficiency requirements as established by the
Energy Policy Act of 1992 (EPACT) effective October 24, 1997.
EVAPORATOR-FAN MOTOR EFFICIENCY
NOTE: All indoor-fan motors 5 hp and larger meet the minimum effi-
ciency requirements as established by the Energy Policy Act of 1992
(EPACT) effective October 24, 1997.
UNIT
579F
UNIT
VOLTAGE
MAXIMUM
ACCEPTABLE
CONTINUOUS
BHP*
MAXIMUM
ACCEPTABLE
CONTINUOUS
BkW*
MAXIMUM
ACCEPTABLE
OPERATING
WATTS
MAXIMUM
AMP DRAW
180
208/230
4.25
3.17
3,775
10.5
460
4.25
3.17
3,775
4.8
575
3.45
2.59
3,065
3.9
216
208/230
5.90
4.40
5,180
15.8
460
7.9
575
6.0
240
208/230
8.70
6.49
7,915
22.0
460
9.50
7.08
8,640
13.0
575
8.70
6.49
7,915
10.0
300
208/230
10.20
7.61
9,510
28.0
460
11.80
8.80
11,000
14.6
575
10.20
7.61
9,510
13.0
BHP — Brake Horsepower
BkW — Brake Kilowatts
UNIT
579F
MOTOR EFFICIENCY
(%)
180 (3.0 Hp)
81.7
180 (3.7 Hp)
85.8
216 (5 Hp)
87.5
240 (7.5 Hp)
88.5
300 (10 Hp)
89.5