PERFORMANCE DATA (cont)
ACCESSORY/FIOP STATIC PRESSURE (in. wg)* — 580F180-300
LEGEND
*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be
used in conjunction with the Fan Performance tables to determine blower rpm and watts.
FAN RPM AT MOTOR PULLEY SETTINGS*
*Approximate fan rpm shown.
†Indicates standard drive package.
**Indicates alternate drive package.
††Due to belt and pulley size, pulley cannot be set to this number of turns open.
EVAPORATOR-FAN MOTOR PERFORMANCE
LEGEND
*Extensive motor and electrical testing on these units ensures that the full horse-
power (brake kilowatt) range of the motors can be utilized with confidence. Using
your fan motors up to the horsepower (brake kilowatt) ratings shown in this table
will not result in nuisance tripping or premature motor failure. Unit warranty will
not be affected.
NOTE: All indoor-fan motors 5 hp and larger meet the minimum efficiency require-
ments as established by the Energy Policy Act of 1992 (EPACT) effective
October 24, 1997.
EVAPORATOR-FAN MOTOR EFFICIENCY
NOTE:  The EPACT (Energy Policy Act of 1992) regulates energy
requirements for specific types of indoor fan motors. Motors regulated
by EPACT include any general purpose, T-frame (three-digit, 143 and
larger), single-speed, foot mounted, polyphase, squirrel cage induction
motors of NEMA (National Electrical Manufacturers Association) design
A and B, manufactured for use in the United States. Ranging from 1 to
200 Hp, these continuous-duty motors operate on 230 and 460 volt,
60 Hz power. If a motor does not fit into these specifications, the motor
does not have to be replaced by an EPACT-compliant energy-efficient
motor. Variable-speed motors are exempt from EPACT compliance
requirements. Therefore, the indoor-fan motors for these units are
exempt from these requirements.
COMPONENT
CFM
4500
5000
5400
6000
7200
7500
9000
10,000
11,250
EconoMi$er IV and EconoMi$er2
0.040
0.050
0.060
0.070
0.090
0.100
0.110
0.120
0.140
FIOP
Factory-Installed Option
UNIT
580F
MOTOR PULLEY TURNS OPEN
0
1
/
2
1
1
1
/
2
2
2
1
/
2
3
3
1
/
2
4
4
1
/
2
5
5
1
/
2
6
180†
††
††
††
††
1021
1002
984
965
947
928
910
891
873
180**
††
††
††
††
1200
1178
1156
1134
1112
1091
1069
1047
1025
210†
††
††
1095
1077
1058
1040
1021
1002
984
965
947
928
910
210**
††
††
1287
1265
1243
1222
1200
1178
1156
1134
1112
1091
1069
240†
††
††
††
††
1151
1132
1114
1095
1077
1058
1040
1021
1002
240**
††
††
††
††
1369
1347
1325
1303
1281
1259
1237
1215
1193
300†
††
††
1283
1269
1247
1225
1203
1182
1160
1138
1116
1095
1066
300**
††
††
††
††
1551
1524
1497
1470
1443
1415
1388
1361
1332
UNIT
580F
UNIT
VOLTAGE
MAXIMUM
ACCEPTABLE
CONTINUOUS
BHP*
MAXIMUM
ACCEPTABLE
CONTINUOUS
BkW*
MAXIMUM
ACCEPTABLE
OPERATING
WATTS
MAXIMUM
AMP DRAW
180
208/230
6.13
4.57
5,180
15.8
460
7.9
575
6.0
210
208/230
5.90
4.40
5,180
15.8
460
7.9
575
6.0
240
208/230
8.70
6.49
7,915
22.0
460
9.50
7.08
8,640
13.0
575
8.70
6.49
7,915
10.0
300
208/230
10.20
7.61
9,510
28.0
460
11.80
8.80
11,000
14.6
575
10.20
7.61
9,510
13.0
BHP
Brake Horsepower
BkW
Brake Kilowatts
UNIT 580F
MOTOR EFFICIENCY
(%)
5 Hp
87.5
7.5 Hp
88.5
10 Hp
89.5