PERFORMANCE DATA (cont)
GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES
1. Values include losses for filters, unit casing, and wet coils. See this
page for accessory/FIOP static pressure information.
2. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using fan
motors up to the wattage ratings shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be
affected. See Evaporator-Fan Motor Performance table on page 79
for additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your
Bryant representative for details.
4. Interpolation is permissible. Do not extrapolate. (Belt drive units
only.)
OUTDOOR SOUND POWER (Total Unit)
NOTE: Indoor sound power is available in Bryant’s Electronic Catalog program (ECAT) for specific operating parameters.
ACCESSORY/FIOP ECONOMIZER IV AND ECONOMI$ER2 STATIC PRESSURE* (in. wg) — 580F036-073
                 LEGEND
*The static pressure must be added to external static pressure. The
sum and the evaporator entering-air cfm should be used in conjunction
with the Fan Performance tables to determine indoor blower rpm and
watts.
ACCESSORY/FIOP ECONOMISER IV AND ECONOMI$ER2 STATIC PRESSURE* (in. wg) — 580F090-151
                 LEGEND
*The static pressure must be added to external static pressure. The
sum and the evaporator entering-air cfm should then be used in con-
junction with the Fan Performance tables to determine blower rpm and
watts.
UNIT 580F
SOUND
RATING
60 Hz (dB)
A-WEIGHTED
(dB)
OCTAVE BANDS
63
125
250
500
1000
2000
4000
8000
036-072
81
80.5
56.8
75.8
72.4
72.9
74.8
75.4
71.3
69.1
073
80
80.0
59.1
68.9
68.7
71.9
74.0
68.9
65.7
59.0
090
87
86.4
83.2
87.4
83.5
82.8
83.0
77.7
71.8
67.0
091, 103
82
82.0
62.2
69.3
71.5
74.7
76.2
72.9
68.7
61.5
120
88
87.6
97.6
90.4
85.7
84.8
83.9
77.5
71.3
65.8
121
84
84.0
64.6
71.7
73.3
76.9
77.6
73.7
70.6
63.7
150
87
86.4
83.7
87.2
83.4
82.8
83.0
77.7
71.8
67.0
151
86
86.0
63.7
69.9
72.5
78.2
81.1
77.3
73.3
66.8
COMPONENT
CFM
1250
1500
1750
2000
2250
2500
2750
3000
Vertical EconoMi$er IV and EconoMi$er2
0.045
0.065
0.08
0.12
0.145
0.175
0.22
0.255
Horizontal EconoMi$er IV and EconoMi$er2
0.1
0.125
0.15
0.18
0.225
0.275
FIOP — Factory-Installed Option
COMPONENT
CFM
2250
2500
2750
3000
3250
3500
3750
4000
4250
4500
4750
5000
5250
6250
Vertical EconoMi$er IV
and EconoMi$er2
0.06
0.075
0.09
0.115
0.13
0.15
0.17
0.195
0.22
0.25
0.285
0.325
0.36
Horizontal EconoMi$er IV 
and EconoMi$er2
0.1
0.125
0.15
0.18
0.21
0.25
0.275
0.3
0.34
0.388
FIOP — Factory-Installed Option
58
0F0
3
6
-15
1