section 6
Diagnostic tests
Page 52
Ground. 12 VDC should be measured. Reconnect Wire 13 to
the SCR. If 12 VDC is NOT measured on Wire 13 Stop Testing
and  repair  or  replace Wire  13  between  the  Starter  Contactor
(SC) and the Starter Contactor Relay (SCR).
Note: Jumper leads may be used if necessary.
4. Set voltmeter to measure resistance.
5. Remove Wire  13, Wire  16,  and Wire  17  from  the  Starter
Contactor Relay (SCR)
6. Connect the meter leads across Terminal 87 and Terminal 30 of
the SCR. See Figure 6-35.
85
87a
30
86
SCR
87
16
15
17
13
00.00
Figure 6-35. – Starter Contactor Relay Test
7. Connect a jumper wire from Terminal 85 to ground. The relay
should energize and the voltmeter should read continuity. See
Figure 6-35.
8. Reconnect all Wires.
RESULTS:
If continuity was not measured in Step 7 replace the 
Starter Contactor Relay. If all steps passed refer back 
to flow chart.
TEST 27 - CHECk START-RUN-STOP SWITCH 
(SW1)
PROCEDURE:
1. Set a voltmeter to measure resistance.
2. Remove all wires from the Start-Run-Stop Switch (SW1).
3. Using  the  chart  below  ohm  out  the  Start-Run-Stop  Switch.
Connect one meter test lead to one terminal and the other meter
test lead to the other terminal. With meter leads connected acti-
vate the switch to Start, Stop or Run and follow the chart.
4. Reconnect all wires to the switch.
  CONDITION 
TERMINALS 
RESULT
STOP
5,4
OPEN
STOP
5,6
CLOSED
STOP
2,1
OPEN
STOP
2,3
CLOSED
RUN
ALL CONDITIONS
OPEN
START
5,4
CLOSED
START
5,6
OPEN
START
2,1
CLOSED
START
2,3
OPEN
167
STOP
0
15
15
17
4
5
6
1
2
3
RUN
START
0
Figure 6-36. – Start-Run-Stop Switch (SW1)
RESULTS:
If  the  switch  fails  any  part  of  the  test  procedure 
replace the switch. 
TEST 28 - CHECk START-RUN-STOP SWITCH 
(SW1) WIRINg
PROCEDURE:
1. Set voltmeter to measure resistance.
2. Remove Wire  17  from  the  Starter  Contactor  Relay  (SCR).
Connect one meter test lead to Wire 17. Remove Wire 17 from
the Start-Run-Stop Switch (SW1). Connect the other meter test
lead to wire 17. Continuity should be measured.
3. Remove both Wire 0 from the Start-Run-Stop switch (SW1) it is
located in two positions on the switch. Connect one meter test
lead to one Wire 0 and connect the other meter test lead to the
other Wire 0. Continuity should be measured.
4. Remove Wire  0  from  the  Start-Run-Stop  switch  (SW1)  it  is
located in two positions on the switch. Connect one meter test
lead  to  one Wire  0  and  connect  the  other  meter  test  lead  to
frame ground. Continuity should be measured.