Simulation Mode 
This mode deactivates network communication Information Updates.  It 
can be combined with any of the three previous modes (example: 
using the Simulation mode when in Debug mode allows the user to test 
the entire system [groups, events, etc] without triggering any actions or 
using any additional material such as gases).  It allows gas 
concentrations to be simulated over an associated scale for each 
transmitter, sequentially: 
 
Alarm levels A, B and C are evaluated according to the simulated gas 
concentration and events are evaluated and actions are taken. 
 
This type of alarm simulation at the controller does not work with 
certain transmitters with falling alarms. In these cases, an alarm can be 
simulated at the transmitter. 
 
While in simulation mode, the controller is unaware of the device’s 
actual network status.  This mode can be stopped at any time in the 
Test menu (see Normal System Operation). 
 
If one of these modes has been activated, the system will automatically 
return to Normal Mode after 12 hours of inactivity. (No changes will be 
lost.) 