Honeywell 301C Manual De Usuario

Descargar
Página de 107
Honeywell 301C User Manual 
XNX and XCD 
 
 
  
Group
Property
Data Type
Required
1
Storage 
Type
2
BACnet 
Writeable?
Value
object_identifier
R
C
N
Modbus address * 256 + 1.  For example an 
XNX at Modbus address 010 will appear as 
2561 or 0x0A01.
object_type
enumerated
R
C
N
analog_input (0)
event_state
enumerated
R
R
N
if gas sensor fault Fault (1),
else normal (0)
object_name
character string
R
N
N
"SSS GGGG   AdAAA.GGGGG" where SSS is 
the sensor type, GGGG is the gas name and 
AAA is the Modbus address.  Gas names are 
truncated to 4 and 5 characters.  Values for 
sensor type are "XNX" or "XCD" For 
example, an XNX at address 10 with a 
Methane sensor will populate this object 
name with "XNX Meth Ad010.Metha"
out_of_service
boolean
R
R
N
FALSE
present_value
real
R
R
N
Gas reading
reliability
enumerated
O
R
N
As appropriate reports
no_fault_detected (0) or
unreliable other (7)
Fault is detected within 60 seconds
status_flags
in_alarm
boolean
R
R
N
if faulty "true" (1)
else "false" (0)
fault
boolean
R
R
N
if faulty "true" (1)
else "false" (0)
overridden
boolean
R
R
N
"false" (0)
out_of_service boolean
R
R
N
"false" (0)
units
enumerated
R
N
N
96 (ppm) or
98 (percent) or
95 (no_units)
Notes
1  --  'R' indicates that this property is required by ASHRAE Standard 135
'O' indicates that the property is optional in ASHRAE Standard 135
2 --  'C' indicates the property is hard-coded as a constant
'N' indicates the property is stored in non-volatile memory
'R' indicate the property is computed constantly and stored in RAM.
continued…
ana
lo
g_
input
gas