Honeywell 301C Manual De Usuario

Descargar
Página de 107
Honeywell 301C User Manual 
EC-FX 
 
Group
Property
Data Type
Required
1
Storage 
Type
2
BACnet 
Writeable?
Value
object_identifier
R
C
N
Modbus address * 256 + 1.  For example an 
EC-F9 at Modbus address 003 will appear as 
769 or 0x0301.
object_type
enumerated
R
C
N
analog_input (0)
event_state
enumerated
R
R
N
if gas sensor fault Fault (1),
else normal (0)
object_name
character string
R
N
N
"EC-F9 GGGG   AdXXX.GGGG" where GGGG 
is the gas name and XXX is the Modbus 
address.  The gas name is often  "NH3".
out_of_service
boolean
R
R
N
FALSE
present_value
real
R
R
N
Gas reading
an
al
og
_i
np
ut
gas
reliability
enumerated
O
R
N
As appropriate reports
no_fault_detected (0) or
unreliable other (7)
Fault is detected within 60 seconds
status_flags
in_alarm
boolean
R
R
N
if faulty "true" (1)
else "false" (0)
fault
boolean
R
R
N
if faulty "true" (1)
else "false" (0)
overridden
boolean
R
R
N
"false" (0)
out_of_service boolean
R
R
N
"false" (0)
units
enumerated
R
N
N
Usually ppm (96) 
object_identifier
R
N
N
Modbus address * 256 + 2.  For example an 
EC-F9 at Modbus address 003 will appear as 
770 or 0x0302.
object_type
enumerated
R
C
N
analog_value (2)
event_state
enumerated
R
C
N
normal (0)
object_name
character string
R
N
N
"EC-F9 GGGG   AdXXX.Amin" where GGGG is 
the gas name and XXX is the Modbus 
address.  The gas name is often  "NH3".
out_of_service
boolean
R
C
N
FALSE
present_value
real
R
N
Y
Gas threshold.  Synchronization is 
maintained with the 301C and the EC-F9.  
Whichever value is written last is 
distributed to the other two locations.
reliability
enumerated
O
C
N
no_fault_detected (0)
status_flags
in_alarm
boolean
R
C
N
always false (0)
fault
boolean
R
C
N
always false (0)
overridden
boolean
R
C
N
always false (0)
out_of_service boolean
R
C
N
always false (0)
units
enumerated
R
C
N
Usually ppm (96) 
object_identifier
R
N
N
Modbus address * 256 + 3.  For example an 
EC-F9 at Modbus address 009 will appear as 
771 or 0x0303.
object_type
enumerated
R
C
N
analog_value (2)
event_state
enumerated
R
C
N
normal (0)
object_name
character string
R
N
N
"EC-F9 GGGG   AdXXX.Amax" where GGGG is 
the gas name and XXX is the Modbus 
address.  The gas name is often  "NH3".
out_of_service
boolean
R
C
N
FALSE
present_value
real
R
N
Y
Gas threshold.  Synchronization is 
maintained with the 301C and the EC-F9.  
Whichever value is written last is 
distributed to the other two locations.
reliability
enumerated
O
C
N
no_fault_detected (0)
status_flags
in_alarm
boolean
R
C
N
always false (0)
fault
boolean
R
C
N
always false (0)
overridden
boolean
R
C
N
always false (0)
out_of_service boolean
R
C
N
always false (0)
units
enumerated
R
C
N
Usually ppm (96) 
Notes
1  --  'R' indicates that this property is required by ASHRAE Standard 135
'O' indicates that the property is optional in ASHRAE Standard 135
2 --  'C' indicates the property is hard-coded as a constant
'N' indicates the property is stored in non-volatile memory
'R' indicate the property is computed constantly and stored in RAM.
continued…
An
al
og
 V
al
ue
s
Ami
n
Am
ax
90