10-Pump, 80-Station Controller           Chapter 4: Operation 
60 
                 
 
 
 
 
10. When you enter the second pump number, the controller checks to make sure that 
both pumps are offline and that the standby pump has no stations assigned to it. If 
these conditions are not all met, error messages appear on the screen instead of a 
Press To Move Stations
 button. If you get an error message, first check to 
make sure that you have entered the correct numbers and reenter if necessary.  
If the error message tells you to disable the source pump and/or the standby pump, touch 
Return
 at this screen, then Pumps at the Pump n Setup screen. Take the pumps offline and 
then return to the Transfer to Standby Pump screen.  
If the error message tells you that the standby pump has stations assigned, you must either use 
a different standby pump or you must remove the pump assignment for all stations assigned 
to the standby pump. To remove the assignments, touch Return at this screen, then 
Stations
 at the Pump n Setup screen. 
Hold a station icon to go to its Station Operator screen, then touch Setup to go to the Station n 
Setup screen. Use ◄ Back. and Next ► to review all pump assignments and, where 
necessary, choose Assigned to Pump x to set station assignments to 0 (unassigned). 
Then return to the Transfer to Standby Pump screen. 
 
1.  Touch Transfer To Standby Pump. 
“Transfer in Progress” appears briefly on the screen, followed by “Transfer 
Complete,” in place of the Transfer To Standby Pump button. The controller 
switches the setting for Source Pump to the new pump and switches the setting for 
Standby Pump
 to 0 (unassigned). 
2.  Touch Return
The Pump n Setup screen appears. 
3.  Touch Pumps
The Pump Status screen appears. 
4.  Put the standby pump online by briefly touching its icon. 
The icon changes color to show the new status, and the system begins using the 
pump. In addition, all Station n Operator and Setup screens show the new pump 
assignment. 
When the failed pump is operational again, you can repeat this process, this time using the 
standby pump’s number as the setting for Source Pump the repaired pump’s number as the 
setting for Standby Pump