F-26748-6
Wiring Requirements
Control and Power Leads
Remove blue plastic thread protectors before installing conduit fittings. See Figure-1 throug
Figure 8 for typical wiring applications and Table-3 for maximum wire lengths.
Caution: The 24 Vac model contains a half-wave rectifier power supply and must not be 
powered by transformers used to power other devices utilizing non-isolated full-wave 
rectifier power supplies. Refer to EN-206 Guidelines for Powering Multiple Full-Wave and 
Half-Wave Rectifier Devices from a Common Transformer
, F-26363, for further information.
Note: Class 2 control and power lead wiring must be routed separately from line voltage 
wiring and any other non-class 2 circuits.
Table-3 Control and Power Wiring Data.
Table-4 Wire Color Codes for Models Manufactured before December, 2007.
Figure-13 Installation of Universal Shaft Extension.
Actuator
 Anti-rotation 
Bracket 
(included with 
actuator)
AM-753 
Universal 
Mounting 
Clamps
Duct
V-clamp
Mounting Surface
Damper Shaft
AM-676 
Universal Shaft 
Extension
1
1  The AM-676 extends the 
damper shaft approximately 
9" (229 mm).
Actuator
Voltage
Part
Number
Maximum Wire Run in ft. (m)
(5% Voltage Drop)
14 AWG
16 AWG
18 AWG
24 Vac and 
22-30 Vdc
MS40-7173
981
(299)
617
(188)
388
(118)
120 Vac
MS40-7170
240 Vac
MS40-7171
Part Number
Power
Voltage
L1
L2
Ground
24 H
24 G
Analog 
Input
500 Ohms
Common
MS40-7173-0-0-0
Old Design
24 Vac
N/A
N/A
Green/Yellow
Black
Black/Blue
White
Red
Black
MS40-7170-0-0-0
Old Design
120 Vac
Black
White
Green/Yellow
N/A
N/A
White 
Red 
Black
MS40-7171-0-0-0
Old Design
240 Vac
Brown
Light 
Blue
Green/Yellow
N/A
N/A
White Red
Black
N/A: Not Applicable