INSTALLATION
Inspection
Inspect the package for damage. If damaged, notify the appropriate carrier immediately.
If undamaged, open the package and inspect the device for obvious damage. Return 
damaged products.
Requirements
Job wiring diagrams
Tools (not provided)
– Socket wrench 1/2 inch, used for universal mounting clamp nuts
– Open-end wrench 10 mm, used for installing AM-676 universal shaft extension
– Slotted screwdriver, used for installing anti-rotation brackets
– Allen wrench 3/16", used for manual override
Appropriate accessories
– Water tight 1/2 inch conduit seals TAC part number TF-711-02 or T&B #5332 
(straight, TAC part number TF-713-02 or T&B #5352 (90°), or equivalent.
– Water tight 1/2 inch flexible conduit (e.,g. Anaconda: Sealtight) or 20 mm flexible 
water tight conduit when using AM-756 metric conduit adapter with appropriate 
metric water tight seals.
– Water tight 1/2" flexible conduit (Anaconda: Sealtight) or 20 mm flexible water tight 
conduit when using AM-756 metric conduit adaptor
– Two #8 1/2" (13 mm) sheet metal screws for mounting (optional)
Training: Installer must be a qualified, experienced technician
4 to 20 mA DC
Controller
(+) 4 to 20 mA DC
(-) Common DC
Power
GRD
GRD
1
1
2
MS40-717X
MS40-717X
1  Unused conduit port must remain plugged with a 
water tight pipe plug as shipped from factory to 
maintain NEMA Type 4 or IP56 rating.
2  See table for power wire designations.
3  Both actuators must be set to operate in the same 
direction.
Yellow/Black  
AI 
Gray  
Blue  
AO 
Yellow/Black  
AI 
Gray  
Blue  
AO 
Position Feedback (-)
Signal 2 to 10 Vdc (+)
COM 
COM 
3
3
4
4
4  Color coding of wiring on older models (MX40-717x-0-
0-0) manufactured prior to December, 2007, differs 
from current models. See Table 4 on page 14. Consult 
label on product to confirm wiring codes.
5  Keep AI, COM and AO wiring less than 30 meters 
length to meed CE requirements.
5
5
Green/Yellow
Green/Yellow
500 Ohm
Figure-8 Typical 4 to 20 mAdc Control Wiring For Two Actuators On The Same Damper Shaft.
Power Wiring Identification.
Voltage
Designation
Wire Color
24 Vac or
22-30 Vdc
24H (DC+)
Red
24G (DC-)
Black
120 Vac
L1
Black
L2
White
240 Vac
L1
Brown
L2
Light Blue