Troubleshooting 
Use the table below to troubleshoot minor power system installation and operational 
problems.  If you still cannot solve a problem, contact your local Powerware DC product 
representative for assistance. 
Problem 
Possible Cause/s 
Required Action 
All rectifiers are off 
(no LEDs on) and 
SM45 display is blank 
AC power to the system is off 
and the batteries are fully 
discharged or disconnected. 
Restore AC power. 
AC power to rectifier(s) off or 
one or more phases are off 
Restore AC power. 
Rectifier is not fully inserted. 
Check that the rectifier is fully 
inserted. 
Green LED of one or 
more rectifiers is off 
Internal rectifier fault 
Remove the rectifier and insert 
another one in the same slot. 
If the second rectifier operates 
normally, the first rectifier is 
faulty and must be returned to 
your local Powerware DC 
product representative. 
Very low AC voltage or AC 
supply failed 
Check the AC supply.  The 
power system will return to 
normal operation when the AC 
supply has returned to within its 
specified AC input voltage 
range.  See Appendix C. 
AC overvoltage 
None.  The power system will 
return to normal operation when 
the AC supply has returned to 
within its specified AC input 
voltage range, as specified in 
Appendix C. 
Rectifier shut down 
Check if a rectifier has in fact 
been shut down, using DCTools.  
If yes, turn on the rectifier using 
DCTools
Rectifier(s) failed 
Use DCTools to determine if a 
rectifier has failed or has been 
shut down. 
If a rectifier has failed, replace it. 
If a rectifier has been shut down, 
refer to required action for 
Rectifier Shut Down. 
Rectifier red LED on 
DC overvoltage 
Remove and re-insert rectifier(s) 
after approximately 5 seconds.