Eaton Electrical SC200 Manual De Usuario

Descargar
Página de 78
Troubleshooting 
 
Copyright © 2005-2006 Eaton Corporation.  All Rights Reserved. 
IPN 997-00012-41D    December 2006 
7-5
 
Problem 
Possible Cause/s 
Required Action 
Missing configuration 
Download the appropriate 
configuration file into the SM45. 
Invalid configuration 
Contact your local Powerware 
DC product representative. 
SM45 displays 
Config Error 
Incorrect number of cells in a 
battery string – a result of a 
mismatch between string 
voltage and nominal rectifier 
output voltage. 
Check the number of cells in a 
battery string, nominal voltage 
of each cell and the nominal 
voltage of the rectifiers. 
SM45 displays 
???
 
Incorrectly configured, 
disconnected or failed sensor 
Configure, connect or replace 
sensor.