Integrated Flow Control 
76
312779E
Global FC Data Copy
Set Global FC Data Copy to Start on thManual Over-
ride Screen
 (s
ee F
. 87). Global copy provides a start-
ing point for all recipes, enabling Continuous Learning 
(see page 76) to take over. 
Global copy works very well with multiple colors when 
the viscosities are similar. It may only require a calibra-
tion and global copy each time a regulator is serviced or 
if restriction downstream of the regulator is changed.
Continuous Learning
The flow profile will automatically adjust as necessary to 
drive to the required flow set point, reflecting changes in 
material viscosity or system dynamics (such as restric-
tions downstream from the regulator). 
When changing recipes, the profile is saved to the cur-
rent active recipe. A Job Complete input will also save 
the profile to the active recipe.
Setting Ki and Kp
. 89 shows the definition and relationship between Ki 
and Kp.
The default value for Ki is 40.
The default value for Kp is 400.
For most applications, Ki and Kp do not need to change. 
Do not change these vallues unless you are sure it is 
required.
Before adjusting these values, ensure that the input fluid 
pressure to the regulator is pulsation free, and the outlet 
pressure is higher than 12 psi (.08 MPa, 0.84 bar) for 
each flow rate set point.
Applications with viscosities less than 20 cps or greater 
than 300 cps may require that the Ki and Kp be 
adjusted. Do this by making small variable changes to 
the values in Advanced Setup Screen 5. See F
IG
. 88.
F
IG
. 87. Manual Override Screen
F
IG
. 88. Advanced Setup Screen 5 (Automatic Mode 
with Flow Control Only)