System Errors 
58
3A0869H
Alarm Troubleshooting
Alarm and Description
Cause
Solution
CA
Communication Error
The Display Module is not 
communicating with the 
Advanced Fluid Control
Module.
The CAN cable between the Display 
Module and the Advanced Fluid Control 
Module is not connected.
Verify that the cable is correctly con-
nected.
The CAN cable is cut or bent.
Verify that the cable has not been cut or 
bent at a radius smaller than 1.6 in. 
(40 mm).
The cable or connector failed.
Replace cable.
Alternator Powered Systems:
Check that the Advance Fluid Control 
Module (AFCM), Display Module (DM), 
and USB Module have power (green 
LED) and are communicating (amber 
LED blinking)
1.
For any module that does not have 
power, disconnect and check the 
voltage on the cable produced by 
the alternator module (See Alterna-
tor Module Power Output). If the 
proper voltage is not detected, trou-
bleshoot the Alternator Module.
2.
If the proper voltage is detected, 
verify the cable connecting the two 
modules is good.
3.
If the cable is good, replace the 
module.
There may be a short in one of the sole-
noid/meter cables connected to the 
AFCM.
Replace the cable (16E890)
The AFCM power supply may be bad, as 
indicated by the status LEDs (red, yellow, 
green) being off. Verify the power supply 
works by disconnecting from the AFCM 
and connecting to another module, either 
the Display Module or USB Module.
Replace the module.
The DM and the AFCM have different ver-
sions of software installed.
Install the latest software from token kit 
16D922 on all modules.
The red LED on the AFCM is on.
If on solid, replace module.
If blinking, contact your distributor.
NOTE:
1.
If the AFCM loses communication (no flickering amber LED) but then comes 
back on the alarm will auto clear and will not log the alarm.
2.
If the DM loses communication (no flickering amber LED) but then comes back 
on you will have to manually clear the alarm and there will be an alarm log.
3.
If the USB module loses communication (no flickering amber LED) but then 
comes back on you will not get an alarm.
CAU1
USB Communication Error
The system detected a USB 
Module at last power up, but 
does not detect it currently.
The module has been removed.
Put system in standby and install the 
USB Module.
The cable is disconnected or broken.
Put system in standby and reconnect or 
replace the USB cable.