Emerson 2200S Manuel D’Utilisation

Page de 158
136
Micro Motion
®
 Model 2200S Transmitters
Connecting with ProLink II Software
To make a HART/Bell 202 connection using ProLink II:
1. Attach the HART signal converter to the serial or USB port of your PC.
2. To connect to a HART multidrop network, connect the HART signal converter leads to any 
point on the network (see Figure D-1). The HART/Bell 202 connection is polarity-insensitive.
To connect to the HART clips:
a.
Remove the transmitter housing cover (see Section C.3). 
b.
Connect the HART signal converter leads to the HART clips on the face of the transmitter 
(see Figure D-2). The HART/Bell 202 connection is polarity-insensitive. You can connect 
either lead to either clip.
Note: The HART clips on the face of the transmitter are connected to the transmitter’s mA/HART 
terminals. You may connect directly to the mA/HART terminals (terminals 1 and 2) if you have 
removed the user interface module.
Figure D-1
HART/Bell 202 connections to network
VIA
TOR
DCS or 
PLC
mA output wiring
Connection is polarity-insensitive