Rosemount 4500
AMS
Right click on the device, select “Device Configuration”, then select 
“Alarm/Saturation Levels,” then “Alarm Levels” from the menu
.
1. Click Next after setting the control loop to manual.
2. Click Next after acknowledging the current alarm levels.
3. Select the desired alarm settings: NAMUR, Rosemount, Other 
4. If “Other” is selected, enter desired “HI Value” and “LO Value” custom 
values. 
5. Click Next to acknowledge new alarm levels.
6. Select Next to acknowledge the loop can be returned to automatic 
control.
7. Select Finish to acknowledge the method is complete.
8. Right click on the device, select “Device Configuration,” then select 
“Alarm/Saturation Levels,” then “Alarm Levels” from the menu
.
9. Select Saturation Levels.
10. Repeat steps 2 - 8 to configure saturation levels.
Alarm and Saturation 
Levels for Burst Mode
Transmitters set to burst mode handle saturation and alarm conditions 
differently.
Alarm Conditions:
Analog output switches to alarm value
Primary variable is burst with a status bit set
Percent of range follows primary variable 
Temperature is burst with a status bit set
Saturation:
Analog output switches to saturation value
Primary variable is burst normally
Temperature is burst normally
Alarm and Saturation 
Values for Multidrop 
Mode
Transmitters set to multidrop mode handle saturation and alarm conditions 
differently.
Alarm Conditions:
Primary variable is sent with a status bit set
Percent of range follows primary variable 
Temperature is sent with a status bit set
Saturation:
Primary variable is sent normally
Temperature is sent normally