Rosemount 4500
3-20
AMS
Right click on the device and select “Diagnostics and Test,” then “Loop test” 
from the menu
.
1. Click Next after setting the control loop to manual.
2. Select desired analog output level. Click Next.
3. Click Next to acknowledge output being set to desired level.
4. Check the reference meter installed in the test loop to verify that it 
displays the commanded output value. 
a. If the values match, the transmitter and the loop are configured and 
functioning properly. 
b. If the values do not match, the current meter may be attached to the 
wrong loop there may be a fault in the wiring, the transmitter may 
require an output trim, or the reference meter may be 
malfunctioning.
After completing the test procedure, the display returns to the loop test screen 
to choose another output value or to end loop testing.
5. Select End and click Next to end loop testing.
6. Select Next to acknowledge the loop can be returned to automatic 
control.
7. Select Finish to acknowledge the method is complete.
ADVANCED FUNCTIONS 
FOR HART PROTOCOL
Saving, Recalling, and 
Cloning Configuration 
Data
Use the cloning feature of the HART Communicator or the AMS “User 
Configuration” feature to configure several 4500 transmitters similarly. Cloning 
involves configuring a transmitter, saving the configuration data, then sending 
a copy of the data to a separate transmitter. Several possible procedures exist 
when saving, recalling, and cloning configuration data. For complete 
instructions refer to the HART Communicator manual (publication no. 
00809-0100-4276) or AMS on-line guides. One common method is as follows:
HART Communicator
1. Completely configure the first transmitter.
2. Save the configuration data:
a. Select F2 SAVE from the HART Communicator HOME/ONLINE 
screen.
b. Ensure that the location to which the data will be saved is set to 
MODULE. If it is not, select 1: Location to set the save location to 
MODULE.
c. Select 2: Name, to name the configuration data. The default is the 
transmitter tag number.
d. Ensure that the data type is set to STANDARD. If the data type is 
NOT STANDARD, select 3: “Data Type”, to set the data type to 
STANDARD.
e. Select F2 SAVE.
3. Connect and power the receiving transmitter and HART Communicator.
Fast Keys
left arrow, 1, 2