Daniel 3812 Liquid Ultrasonic Flow Meter Installation Manual
Section 3: Electrical installation
3-9000-765 Rev H
May 2015
Seal the Junction Box remote mount electronics option
 65
3.7.3
Seal the Junction Box remote mount electronics option
Use the following instructions to install the security seal wire on the junction box, if required.
Procedure
1.
Install security wire seal into and through two of the four the holes in the socket head 
screws on the Junction Box cover (maximum wire diameter .078 inch; 2.0 mm). 
Figure 3-11  3812 Remote mount transmitter electronics option
2.
Position the wire to prevent counterclockwise rotation of the screws when the seal wire 
is taut.
3.
Twist and adjust wire removing all slack and seal.
4.
Cut wire ends to remove excess wire.
5.
This completes installing security seals on the Junction Box.
A.
A. Junction Box socket head screws