Using AMS Device Manager to configure the meter
Section 4: Configuration
Daniel 3410 Series Ultrasonic Gas Flow Meter Installation Manual
June 2014
3-9000-759 Rev D
AMS Device Manager - Guided Setup 
The Guided setup wizard provides configuration parameter settings for the meter. The Guided 
Setup is a subset of the Manual Setup parameters. 
Figure 4-5  AMS Device Manager - Guided Setup  
Note
:  Before writing configuration changes to your meter, make sure you have saved 
the Configuration file and Maintenance log.
Procedure
1.
Disable the Write Protect switch in the CPU Module to write any of the following 
configuration parameters to your meter.
2.
Click the 
Setup Units
 tab to configure the system units (U.S. Customary or Metric units), 
Volume units, Flow rate time units, Velocity units, Pressure units and Temperature 
units. Click Apply to write the parameters to the meter.
3.
Click the 
Setup Outputs
 tab to configure the Device Variables Mapping, Units, 
Frequency/Digital outputs, Frequency and Digital Outputs 1 and 2, Analog outputs, 
Digital Input, Pressure and Temperature.
a.
Analog output 1 (HART) -  
Content
 
(Primary Variable)
 displays Uncorrected Flow 
Rate and is a read only attribute). Configure 
Direction
 (flow), 
Lower Range value
Upper range value
 and 
Alarm Action 
and view the 
HART Parameters 
Tag, Date, 
Descriptor, Message, Final Assembly Number Poll Address, Number of Response 
Preambles.
b.
Analog Output 2 -  
Content
 
(Secondary Variable)
 displays Uncorrected Flow Rate 
and has a read only attribute.  Configure 
Direction
 (flow), 
Lower Range value
Upper range value
 and 
Alarm Action. 
Map the Third and Four variables using the 
Manual Setup wizard. Selections include Uncorrected Volume Flow Rate, 
Pressure and Temperature.