Daniel 3410 Series Ultrasonic Gas Flow Meter Installation Manual
Section 4: Configuration
3-9000-759 Rev D
June 2014
Field Setup Wizard
 75
8.
The Meter Corrections page allows you to configure the flow profile, temperature, 
pressure and linear expansion corrections, pipe outside diameter The Young’s Modulus 
value (ratio of tensile stress to tensile strain) and the Poisson’s ratio value (the absolute 
ratio of the pipe material lateral strain over axial strain) for 3412 and 3411 Gas 
Ultrasonic Flow meters. Click 
Next
 to continue to the Temperature and Pressure page.
9.
Set the temperature and pressure scaling for analog inputs, enter fixed values, and set 
alarm limits for both. The alarm limit selections are hold last output value or use fixed 
value.
Live temperature selections include minimum and maximum inputs or fixed 
temperature.
Live pressure selections include minimum and maximum inputs, gage 
(atmospheric pressure), absolute, or fixed pressure.
Click Next to continue to the Gas Chromatograph Setup page.
10.
Select the settings below to configure a serial port as a Modbus Master to poll a gas 
chromatograph.
Serial Port:
 
select which serial port will be connected to the GC. While the port is 
configured for communications to a GC, it will not act as a Modbus slave device 
for communications from Daniel MeterLink™ or a SCADA system.
GC protocol: select the protocol for which the GC is configured. The Daniel Gas 
Ultrasonic meter uses 7 data bits, Even parity, and 1 stop bit for ASCII Modbus 
and 8 data bits, No parity, and 1 stop bit for RTU Modbus
GC baud rate: select the baud rate for which the GC is configured.
GC comms address: enter the Modbus ID of the GC.
GC stream number: enter the stream number for the gas composition the Daniel 
Gas Ultrasonic meter will read.
GC heating value units: elect the units for which the heating value is configured 
in the GC.
Use which gas composition on GC alarm: select which gas composition the 
Daniel Gas Ultrasonic meter will use if the GC goes into alarm. If Fixed value is 
selected, the meter will start using the fixed gas composition stored in the meter. 
If Last good value is selected, the meter will use the last gas composition 
collected from the GC before the GC started to report alarms. Click Next to 
continue to the AGA8 page.