3.5.2.4. Narrow Echo Filter (default 0)
Filters out echoes of a specific width.
To remove a false echo from the Echo Profile, take its width in mm and
multiply it by 0.014. Enter the result.
For example, to filter out a spike with 500 mm width enter 7 (the sum of 500
x 0.014).
When a value is keyed in, the nearest acceptable value is entered.
multiply it by 0.014. Enter the result.
For example, to filter out a spike with 500 mm width enter 7 (the sum of 500
x 0.014).
When a value is keyed in, the nearest acceptable value is entered.
3.5.2.5. Reform Echo (default 0)
Smooths jagged peaks in the echo profile. Reforms fragmented echoes
into one echo.
Use this feature when monitoring solids, if the reported level fluctuates
slightly even though the monitored surface is still.
Enter the amount of smoothing required. When a value is keyed in, the
Enter the amount of smoothing required. When a value is keyed in, the
nearest acceptable value is entered.
3.5.2.6. Echo detection position
The point on the selected echo from which the measured value is taken.
3.5.3. Echo Sampling
3.5.3.1. Window.
A "distance window" centered on the echo, used to derive the reading.
When a new measurement is in the window, the window is re-centered
and the reading is calculated .
When the value is 0, the window is automatically calculated after each
measurement.
measurement.
• For slower Measurement Response values, the window is narrow.
• For faster Measurement Response values, the window becomes
• For faster Measurement Response values, the window becomes
progressively wider.
Values
0 = OFF
greater = wider
greater = wider
Related
Parameters
Parameters
•
•
Values
0 = OFF
Greater = Wider
Recommended range 10 to 20: higher is not recommended.
Greater = Wider
Recommended range 10 to 20: higher is not recommended.
Related
Parame-
ters
Parame-
ters
•
Material
•
•
•
Options
*
CENTER
RISING
RISING