14. EMC AND LOW VOLTAGE DIRECTIVES
14.1.1 Standards relevant to the EMC directive
For all test items, the test has been done with a position board installed in a computer that is compatible to CE
mark.
The test does not cover USB because only the test tool "MRZJW3-MC2-UTL" (sold separately) uses it.
The standards relevant to the EMC Directive are listed in table below.
mark.
The test does not cover USB because only the test tool "MRZJW3-MC2-UTL" (sold separately) uses it.
The standards relevant to the EMC Directive are listed in table below.
Certification
Test item
Test details
Standard value
EN61000-6-4:2007+A1:2011
CISPR16-2-3, CISPR22
Radiated emission
(Note 1)
Radiated emission
(Note 1)
Radio waves from the product
are measured.
are measured.
30M-230MHz QP (Note 2) : 40dBµV/m
(10m (32.81ft.) in measurement range)
230M-1000MHz QP: 47dBµV/m
(10m (32.81ft.) in measurement range)
1GHz-2GHz QP: 76dBµV/m
(3m (9.84ft.) in measurement range)
(10m (32.81ft.) in measurement range)
230M-1000MHz QP: 47dBµV/m
(10m (32.81ft.) in measurement range)
1GHz-2GHz QP: 76dBµV/m
(3m (9.84ft.) in measurement range)
AV: 56dBµV/m
(3m (9.84ft.) in measurement range)
CISPR16-2-1
CISPR16-1-2
Conducted emission
CISPR16-1-2
Conducted emission
Noise from the product to the
power line is measured.
power line is measured.
AC power line
0.15M-0.5MHz QP :
79dBµV
AV (Note 3) : 66dBµV
0.5M-30MHz QP :
73dBµV
AV : 60dBµV
EN61000-6-2:2005
EN61000-4-2
Electrostatic discharge
immunity
Electrostatic discharge
immunity
Immunity test in which
electrostatic discharge is
applied to the product.
electrostatic discharge is
applied to the product.
8kV: 10 times at 1 second interval,
Air discharge
4kV: 10 times at 1 second interval,
Contact discharge
EN61000-4-3
Radiated immunity
(Note 1)
Radiated immunity
(Note 1)
Immunity test in which electric
fields are radiated to the
product.
fields are radiated to the
product.
80%AM modulation @1kHz,
80-1000MHz 10V/m,
1400M-2000MHz 3V/m,
2000M-2700MHz 1V/m
80-1000MHz 10V/m,
1400M-2000MHz 3V/m,
2000M-2700MHz 1V/m
EN61000-4-4
Electrical fast transient/
burst (EFT/B) immunity
Electrical fast transient/
burst (EFT/B) immunity
Immunity test in which burst
noise is applied to the power
cable and signal line.
noise is applied to the power
cable and signal line.
AC power line
DC power line
I/O, communication line
DC power line
I/O, communication line
: ±2kV/5kHz
: ±2kV/5kHz
: ±1kV/5kHz
: ±2kV/5kHz
: ±1kV/5kHz
EN61000-4-5
Surge immunity
Surge immunity
Immunity test in which surge is
applied to the power line and
signal line.
applied to the power line and
signal line.
AC power line
Common mode: ±2.0kV
Differential mode: ±1.0kV
Differential mode: ±1.0kV
DC power line
Common mode: ±0.5kV
Differential mode: ±0.5kV
Differential mode: ±0.5kV
I/O, communication line
Common mode: ±1kV
EN61000-4-6
Conducted immunity
Conducted immunity
Immunity test in which high
frequency noise is applied to the
power line and signal line.
frequency noise is applied to the
power line and signal line.
0.15-80MHz,
80%AM modulation @1kHz, 10Vrms
80%AM modulation @1kHz, 10Vrms
EN61000-4-11
Voltage dip and short
interruptions immunity
Voltage dip and short
interruptions immunity
Immunity test in which short
interruptions are applied to the
power supply voltage.
interruptions are applied to the
power supply voltage.
0% of rated voltage, 1cycle
Start at zero cross
0% of rated voltage, 250/300cycle
(50Hz/60Hz)
40% of rated voltage, 10/12cycle
(50Hz/60Hz)
70% of rated voltage, 25/30cycle
(50Hz/60Hz)
Note 1. This product is an open type device (a device designed to be housed inside other equipment) and must be installed inside a
conductive control panel. The corresponding test has been done with the programmable controller installed inside a control panel.
2. QP: Quasi-peak value
3. AV: Average value