Honeywell MRP-2001 Manuel D’Utilisation

Page de 136
FACP Configuration Templates
Template 10: Dual Hazard - Split Release
112
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
B.4  Template 10: Dual Hazard - Split Release 
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on corresponding 
output circuit).
Input Zone Types: 
Zone 1 = 2-wire smoke
Zone 2 = Fire
Zone 3 = Waterflow  - activation delayed for 10 seconds (Waterflow Delay Timer 10 set to secs.)
Zone 4 = Supervisory
Zone 5 = Manual Release
Zone 6 = Pull Station
Output Circuit Types:
Output 1 = Alarm NAC
Output 2 = Supervisory Bell NAC
Output 3 = Release Solenoid 1 (unsupervised for shorts)
Output 4 = Release Solenoid 2 (unsupervised for shorts)
Timers
Soak Timer 1 - set for 10 minutes
Soak Timer 2 - set for 10 minutes
Waterflow Delay Timer - set for 10 seconds
AC Loss Delay Timer - set for 2 hours
Operation
Activation of Input Zone 1 (2-Wire Smoke) will operate Release Solenoid 1 Output #3 and 
Alarm NAC Output #1.  Activation of Input Zone 2 (Fire) will operate Release Solenoid 2 
Output #4 and Alarm NAC Output #1.  Activation of Input 5 (Manual Release) or Input 6 
(Manual Pull Station) will operate Solenoid 1 Output #3 and Solenoid 2 (Output #4) and 
Alarm NAC Output #1.  Release Solenoid 1 will turn off water release following time-out of 
the 10 minute Soak Timer 1 and Release Solenoid 2 will turn off water release following 
time-out of the 10 minute Soak Timer 2
Activation of Input Zone 3 (Waterflow) will operate the Alarm NAC Output #1.  There is a 
10 second FACP initiated delay in activation since Waterflow Delay Timer is set to 10 
seconds
Activation of Input Zone 4 (Supervisory) will operate the Supervisory Bell NAC Output #2
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation. 
Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3 
(Waterflow - with Waterflow Delay time) or Zone 5 (Manual Release) or Zone 6 (Pull 
Station) will operate Alarm Relay
Trouble Relay - any system trouble will activate the Trouble Relay
Supervisory - activation of Zone 4 (Supervisory) will operate the Supervisory Relay
TEMPLATE 10: DUAL HAZARD - SPLIT RELEASE
INPUT ZONES
1
2
3
4
5
6
OUTPUT CIRCUITS
2-WIRE SMOKE
FIRE
WATERFLOW
SUPV.
MANUAL 
RELEASE
PULL 
STATION
#1 ALARM NAC
X
X
X
X
X
#2 SUPV BELL NAC
X
#3 RELEASE SOLENOID 1
X
X
X
#4 RELEASE SOLENOID 2
X
X
X