Maintenance
Testing & Maintenance
MRP-2001 & MRP-2001E   PN 53040:A  4/16/2007
125
Test i
3
 Series detectors as follows:
Test Switch
1. An opening for the recessed test switch is located on the detector housing.
2. Insert a small screwdriver or allen wrench (0.18” max.) into the test switch opening; push 
and hold.
3. If the detector is within the listed sensitivity limits, the detector’s red LED should light 
within five seconds.
Smoke Entry Test
Hold a smoldering punk stick or cotton wick at the side of the detector and gently blow the smoke 
through the detector until it alarms.
Note:  For the above tests, the detector will reset only after the power source has been momentarily 
interrupted.
If a detector fails any of the above test methods, its wiring should be checked and it should be 
cleaned as outlined in the Maintenance section of the System Sensor Document.  If the detector still 
fails, it should be replaced.
Notify the proper authorities when the system is back in service.
E.2  Maintenance
A regular schedule of inspection, testing and maintenance is vital to ensure proper and reliable 
operation of the control panel.  The procedures should be performed as required by the local 
authority having jurisdiction.  Refer to NFPA documentation for further details.