Chapter 6:  Troubleshooting 
6-1 Introduction 
The utmost in safety precautions should be observed at all times when working on or around 
the machine and the electrical components. All normal trouble-shooting must be 
accomplished with the power off, line fuses removed, and with the machine tagged as out of 
service.  
The use of good quality test equipment cannot be over-emphasized when troubleshooting is 
indicated. Use a good ammeter that can measure at least twice the AC and DC current that 
can be encountered for the machine. Be sure that the voltmeter has at least minimum 
impedance of 5,000 OHMS-per-volt on AC and 20,000 OHMS-per-volt on DC scales. 
Popular combination meters, VOM and VTVM can be selected to provide the necessary 
functions. 
Before making haphazard substitutions and repairs when defective electrical components are 
malfunctioning, we recommend that you check the associated circuitry and assemblies for 
other defective devices. It is common to replace the obviously damaged component without 
actually locating the real cause of the trouble. Such hasty substitutions will only destroy the 
new component. Refer to wiring diagrams and schematics. 
Locating mechanical problems, should they occur, is relatively straightforward. When 
necessary, refer to the parts catalog section. 
 
 
Alarm Message 
Cause 
Corrective Action 
Dryer Status 
VALVE 
POSITION 
FAULT
 
The limit switch on the 
valve may not have 
been wired correctly. 
The switch is indicating the 
incorrect desiccant tank is in 
regeneration. Check the 
wiring of the switch against 
the wiring diagram. Make 
sure all the wire connections 
are tight. 
- Dryer Shuts down: 
- Process blower OFF. 
- Process heaters OFF. 
- Regen heaters OFF. 
- Alarm light is ON 
- Alarm horn is ON. 
Limit switch may be out of 
position. Re-adjust the 
switch to make sure it trips 
when it is at the high 
position, and it does not 
touch the cam when it is at 
the low position. 
VALVE MOTOR 
OVERIDE
 
The valve has made 
enough rotations and 
the correct position of 
the valve was not 
detected. 
Limit switch may be faulty. 
Replace the switch and 
make sure the wires are 
connected correctly. 
- Dryer Shuts down: 
- Process blower OFF. 
- Process heaters OFF. 
- Regen heaters OFF. 
- Alarm light is ON 
- Alarm horn is ON. 
 
 
 
 
 