Auxiliary Area Allocations
Appendix D
A559
00 to 15 Number of Analog Samples
Indicates the number of data samples actually input since sam-
pling started.
A560
00 to 15 Analog Output 1 Output Value
When an END refresh is selected, the 4-digit hexadecimal value 
set here by the user is output from analog output port 1.
When immediate refreshing is selected, the 4-digit hexadecimal 
value being output from analog output port 1 is stored here for 
monitoring. The output value range depends on the output range, 
as shown below.
• 0 to 10 V, 0 to 5 V or 1 to 5 V: FF38 to 1068 hex
−10 to 10 V: EA84 to 157C hex
Note
1. Set the analog output method (END or immediate refreshing) 
with the System Setup’s output method setting. A setting of 0 
hex specifies an END refresh. This setting applies to both ana-
log output 1 and 2.
2. Specify the output range with the output 1 setting.
A561
00 to 15 Analog Output 2 Output Value
This word has the same settings as the analog output 1 output 
value (A560), above. (When an END refresh is selected, set the 
value to output from analog output port 2. When an immediate 
refresh is selected, the output value is stored here for monitoring.)
Note
1. Set the analog output method (END or immediate refresh) with 
the System Setup’s output method setting. A setting of 0 hex 
specifies an END refresh. This setting applies to both analog 
output 1 and 2.
2. Specify the output range with the output 2 setting.
A562
00
Analog Output 1 Flags
User Adjustment 
Completed
Initial value is 0.
Set to 1 if user performs offset/gain adjustment and Returns to 
factory default setting of 0 if adjustment value is cleared.
04
Operating
ON: ON while the analog output is being changed by ACC(888).
OFF: Turned OFF when target value is reached.
08
Output SV Error
ON: ON when the output SV setting is outside of the allowed set-
ting range.
OFF: OFF when the output SV is within range.
12
Factory Adjust-
ment Value 
Error
ON: ON when the factory-set data stored in flash memory is 
invalid.
OFF: OFF when the factory-set data stored in flash memory is 
normal.
14
User Adjustment 
Value Error
ON: ON when the user-set adjustment value stored in flash mem-
ory is invalid.
OFF: OFF when the user-set adjustment value stored in flash 
memory is normal.
A563
00
Analog Output 2 Flags
User Adjustment 
Completed
Same as for Analog Output 1 Flags. 
04
Operating
08
Output SV Error
12
Factory Adjust-
ment Value 
Error
14
User Adjustment 
Value Error
A564
00
Analog Output 1 Conversion Enable Bit
ON: Enables D/A conversion (enables analog output).
OFF: Disables D/A conversion (analog values output according to 
Output Stop Function specification in System Setup).
Note This bit is cleared when the Modules operating mode is 
changed between RUN or MONITOR mode and PROGRAM 
mode. 
A565
00
Analog Output 2 Conversion Enable Bit
ON: Enables D/A conversion (enables analog output).
OFF: Disables D/A conversion (analog values output according to 
Output Stop Function specification in System Setup).
Note This bit is cleared when the Modules operating mode is 
changed between RUN or MONITOR mode and PROGRAM 
mode. 
Address
Bits
Name