NetBotz Room Sensor Pod 155 Installation Manual
Connect Sensors
Only connect sensors supported by the appliance to which the NetBotz 155 is 
connected. See the installation and quick configuration manual included with 
your appliance.
Connect APC and third-party sensors to the four ports labeled Sensors on the 
NetBotz 155.
•  Third-party dry contact sensors require the NetBotz Dry Contact Cable 
(NBES0304). To connect a sensor to the cable, follow the instructions 
provided with the sensor and the instructions provided with the cable.
•  Standard third-party 0-5 V sensors require the NetBotz 0-5 V Sensor 
Cable (NBES0305). To connect a sensor to the cable, follow the 
instructions provided with the sensor and the instructions provided with 
the cable.
•  If a sensor cable is not long enough, use an RJ-45 coupling (provided 
with some sensors) and standard CAT-5 cabling to extend the cable up to 
15 m (50 ft) for a Temperature/Humidity Sensor (AP9335TH) or a 
Temperature Sensor (AP9335T) and up to 30.5 m (100 ft) for all other 
supported sensors.
Configure and Monitor Sensors
Once your system is installed and receiving power, configure sensors and begin 
monitoring your system using the software interface for the appliance.
See your appliance installation and quick configuration manual for 
system installation details and for instructions on accessing the  
software interface of the appliance.