Avaya 03-300430 Manuel D’Utilisation
CAB-TEMP (Cabinet Temperature)
Issue 1 June 2005
753
CAB-TEMP (Cabinet Temperature)
G650
The MO CAB-TEMP monitors the G650 and the 655A for the following:
●
The power supply
- Inlet temperature
- Hot spot temperature status
- Fan speed
- Fan alarm lead
●
The G650 carrier exhaust temperature
The serial bus is used by the TN2312BP IPSI to obtain this information from each power supply
in a G650 media gateway. There is only one outlet temperature sensor and fan assembly in a
G650, so information obtained from dual power supplies (slot 0 and 15) is redundant.
Refer to
in a G650 media gateway. There is only one outlet temperature sensor and fan assembly in a
G650, so information obtained from dual power supplies (slot 0 and 15) is redundant.
Refer to
further information.
Note:
Note:
Fan/filter replacement procedures for the CMC1 and G600 media gateways are
to be found under
to be found under
in Maintenance Procedures (03-300192).
Error log entries and test-to-clear values
MO name (in
alarm log)
alarm log)
Alarm
level
level
Initial SAT command to
run
run
Full name of MO
CAB-TEMP
MIN
test board location
Cabinet Temperature
CAB-TEMP
MAJ
test board location
Cabinet Temperature
Table 259: CAB-TEMP Error Log Entries
Error
Type
Type
Aux
data
data
Associated test
Alarm
level
level
On/Off
board
board
Test-to-clear value
1 (
Power supply
temperature test (#1537)
MIN
OFF
test enviroment location
test board location
test board location
257 (
)
Power supply
temperature test (#1537)
MIN
ON
test enviroment location
test board location
test board location