Design Dynamics VF-24N-MHD Manuel D’Utilisation

Page de 28
www.fmiproducts.com
116986-01H
13
where  trapped  matter  is  not  likely  to  freeze. 
A sediment trap traps moisture and contami-
nants. This keeps them from going into heater 
controls. If sediment trap is not installed or is 
installed wrong, heater may not run properly.
 CAUTION: Avoid damage to 
gas  control.  Hold  gas  control 
with wrench when connecting it 
to gas piping and/or fittings.
CHECkING GAS CONNECTIONS
 WARNING: Test all gas piping 
and  connections,  internal  and 
external to unit, for leaks after 
installing or servicing. Correct 
all leaks at once.
  WARNING:  Never  use  an 
open flame to check for a leak. 
Apply a noncorrosive leak detec-
tion fluid to all joints. Bubbles 
forming show a leak. Correct all 
leaks at once.
 CAUTION: Make sure exter-
nal regulator has been installed 
between  propane/LP  supply 
and heater. See guidelines un-
der Connecting to Gas Supply
page 12.
PRESSURE TESTING GAS SUPPLY 
PIPING SYSTEM
Test  Pressures  In  Excess  Of  1/2  PSIG 
(14" W.C.)
1.  Disconnect  appliance  with  its  appliance 
main gas valve (control valve) and equip-
ment shutoff valve from gas supply piping 
system. Pressures in excess of 1/2 psig 
will damage heater regulator.
2.  Cap off open end of gas pipe where equip-
ment shutoff valve was connected.
3.  Pressurize supply piping system by either 
opening  propane/LP  supply  tank  valve 
for propane/LP gas or opening main gas 
valve  located  on  or  near  gas  meter  for 
natural gas or using compressed air.
INsTallaTIoN
Continued 
Installation must include an equipment shutoff 
valve, union and plugged 1/8" NPT tap. Locate 
NPT tap within reach for test gauge hook up. 
NPT tap must be upstream from heater (see 
Figure 12).
IMPORTANT: Install equipment shutoff valve 
in  an  accessible  location.  The  equipment 
shutoff valve is for turning on or shutting off 
the gas to the appliance.
Check  your  building  codes  for  any  special 
requirements for locating equipment shutoff 
valve to fireplaces.
Apply pipe joint sealant lightly to male NPT 
threads. This will prevent excess sealant from 
going into pipe. Excess sealant in pipe could 
result in clogged heater valves.
  WARNING:  Use  pipe  joint 
sealant that is resistant to liquid 
petroleum (LP) gas.
We  recommend  that  you  install  a  sediment 
trap  in  supply  line  as  shown  in  Figure  12. 
Locate sediment trap where it is within reach 
for cleaning. Install in piping system between 
fuel supply and heater. Locate sediment trap 
*  Purchase  the  optional  equipment  shutoff 
valve  from  your  dealer.  See  Accessories
page 25.
** Minimum inlet pressure for purpose of input 
adjustment. 
Figure 12 - Gas Connection
3" Minimum
Equipment Shutoff Valve 
With 1/8" NPT Tap*
Approved 
Flexible Gas 
Hose (if allowed 
by local codes)
 Cap  Pipe  Tee
    Nipple Joint
Sediment Trap
Natural Gas
From Gas Meter 
(5" W.C.** to 10.5" 
W.C. Pressure)
Propane/LP Gas
From External 
Regulator
(11" W.C.** to
14" W.C.
Pressure)
To Gas 
Control