Desa LCR18NT Manuel D’Utilisation

Page de 56
www.desatech.com
121255-01A
6
DETERMINING FRESH-AIR FLOW 
FOR HEATER LOCATION
Determining if You Have a Confined or 
Unconfined Space
Use this work sheet to determine if you have 
a confined or unconfined space.
Space: Includes the room in which you will install 
heater plus any adjoining rooms with doorless pas-
sageways or ventilation grills between the rooms.
1.  Determine the volume of the space (length 
x width x height).
 
Length x Width x Height =__________cu. ft. 
(volume of space)
 
Example: Space size 20 ft. (6.1 m) (length) x 16 
ft. (4.88 m) (width) x 8 ft. (2.44 m) (ceiling height) 
= 2560 cu. ft. (72.49 m
3
) (volume of space)
 
If  additional  ventilation  to  adjoining  room 
is supplied with grills or openings, add the 
volume of these rooms to the total volume 
of the space. 
2.  Multiply the space volume by 20 to determine 
the maximum Btu/Hr the space can support.
 
  ________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
 
Example: 2560 cu. ft. (72.49 m
3
) (volume of 
space) x 20 = 51,200 (maximum Btu/Hr the 
space can support)
3.  Add the Btu/Hr of all fuel burning appliances 
in the space.
 
Vent-free heater 
  __________ Btu/Hr
 
Gas water heater* 
  __________ Btu/Hr
 
Gas furnace 
  __________ Btu/Hr
 
Vented gas heater 
  __________ Btu/Hr
 
Gas fireplace logs 
  __________ Btu/Hr
 
Other gas appliances*+ __________ Btu/Hr
 
Total 
=  _________ Btu/Hr
 
* Do not include direct-vent gas appliances. 
Direct-vent  draws  combustion  air  from  the 
outdoors and vents to the outdoors.
 
Example: 
 
Gas water heater 
  __________ Btu/Hr
 
Vent-free heater 
+  _________ Btu/Hr
 
Total 
=  _________ Btu/Hr
4.  Compare the maximum Btu/Hr the space can 
support with the actual amount of Btu/Hr used.
 
  _______ Btu/Hr (maximum can support) 
 
  _______ Btu/Hr (actual amount used)
 
Example:  51,200  Btu/Hr  (maximum  the 
space can support)
 
 
60,000 Btu/Hr (actual amount of 
Btu/Hr used)
AIR FOR COMbUSTION 
AND VENTILATION
Continued
The space in the above example is a confined 
space because the actual Btu/Hr used is more 
than  the  maximum  Btu/Hr  the  space  can  sup-
port. You must provide additional fresh air. Your 
options are as follows:
A.  Rework worksheet, adding the space of an 
adjoining room. If the extra space provides 
an unconfined space, remove door to adjoin-
ing  room  or  add  ventilation  grills  between 
rooms.  See  Ventilation  Air  From  Inside 
Building.
B.  Vent  room  directly  to  the  outdoors.  See 
Ventilation Air From Outdoors, page 7.
C.  Install a lower Btu/Hr heater, if lower Btu/Hr 
size makes room unconfined. 
If the actual Btu/Hr used is less than the maxi-
mum Btu/Hr the space can support, the space is 
an unconfined space. You will need no additional 
fresh air ventilation.
 WARNING: If the area in which 
the  heater  may  be  operated  is 
smaller  than  that  defined  as 
an  unconfined  space  or  if  the 
building  is  of  unusually  tight 
construction, provide adequate 
combustion and ventilation air 
by one of the methods described 
in the National Fuel Gas Code, 
ANSI Z223.1/NFPA 54 Section 5.3 
or applicable local codes.
vENTILATION AIR
Ventilation Air From Inside Building
This  fresh  air  would  come  from  an  adjoin-
ing  unconfined  space.  When  ventilating  to 
an  adjoining  unconfined  space,  you  must 
provide two permanent openings: one within 
12"  (30.5  cm)  of  the  ceiling  and  one  within 
12"  (30.5  cm)  of  the  floor  on  the  wall  con-
necting the two spaces (see options 1 and 2, 
Figure 2, page 7). You can also remove door 
into adjoining room (see option 3, Figure 2, 
page 7). Follow the National Fuel Gas Code, 
ANSI  Z223.1/NFPA  54,  Section  5.3, Air  for 
Combustion and Ventilation
 for required size 
of ventilation grills or ducts.
  40,000
  20,000
  60,000