Desa VP1000BT Manuel D’Utilisation

Page de 20
5
102393
OWNER’S MANUAL
Figure 2 - Ventilation Air from Inside Building
Or 
Remove 
Door into 
Adjoining 
Room, 
Option 3
Ventilation Grills 
Into Adjoining Room,
Option 2
12"
12"
Ventilation
Grills
into Adjoining
Room, 
Option 1
 WARNING: Rework work-
sheet, adding the space of the
adjoining unconfined space. The
combined spaces must have
enough fresh air to supply all
appliances in both spaces.
AIR FOR
COMBUSTION AND
VENTILATION
Continued
VENTILATION AIR
Ventilation Air From Inside
Building
This fresh air would come from an adjoining
unconfined space. When ventilating to an
adjoining unconfined space, you must pro-
vide two permanent openings: one within
12" of the ceiling and one within 12" of the
floor on the wall connecting the two spaces
(see options 1 and 2, Figure 2). You can also
remove door into adjoining room (see op-
tion 3, Figure 2). Follow the National Fuel
Gas Code NFPA 54/ANSI Z223.1, Section
5.3, Air for Combustion and Ventilation
 for
required size of ventilation grills or ducts.
Figure 3 - Ventilation Air from Outdoors
Outlet
Air
Ventilated
Attic 
Outlet
Air
Inlet
Air
Inlet Air
Ventilated 
Crawl Space
To 
Crawl
Space
To Attic
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation
grills or ducts. You must provide two per-
manent openings: one within 12" of the
ceiling and one within 12" of the floor.
Connect these items directly to the outdoors
or spaces open to the outdoors. These spaces
include attics and crawl spaces. Follow the
National Fuel Gas Code NFPA 54/ANSI
Z223.1, Section 5.3, Air for Combustion and
Ventilation
 for required size of ventilation
grills or ducts.
IMPORTANT:
 Do not provide openings for inlet or outlet air into attic if attic has a
thermostat-controlled power vent. Heated air entering the attic will activate the power vent.