Wiring 
 
All field wiring should be routed up through the knockout 
in the bottom panel or in the back of the unit.   
 
 
Supply Power.
 
 
1.  Insure that minimum circuit ampacity is 15 amps. 
2.  Terminals are provided in the electrical compartment 
for field connection of the main power supply legs 
(single phase) and a ground wire. 
3.  Install external overcurrent protection and provide 
wiring in accordance with the NEC, state and local 
codes.  
4.  Power supply must be “clean”: free of spikes, surges 
and sags: +10%, -15% of nominal.  
 
                         Electrical Characteristics 
Capacity 
Steam  Output 
Lbs. / hr 
Kg / hr 
1.8 
3.7 
 
Input kW 
 1.33 
2.66 
Volts/Ph: Amps 
120/1 11.8  N/A 
230/1 5.9  11.8 
 
 
 
 
 
 
 
 
 
 
Control Circuit Connections 
WARNING! 
Do Not install any controls inside the
Herrmidifier 6000 cabinet. Installations of any
extraneous devices inside the electrical
compartment rnay cause erratic behavior of the
circuitry and will VOID the warranty. 
6000-1,2 
The 6000 units with built-in blowers require no external 
control wiring since the humidistat and air proving switch 
are built-in. 
 
6000-3,4 
The control wiring for the ducted version is to be 
connected to the 5 pole controls terminal strip located in 
the low voltage compartment. Terminals #1 and #2 are 
for connecting the control and high limit humidistats as 
well as the air proving switch in series (all included). If 
desired, terminals #3 and #4 are relay contacts to 
energize your fan relay (Relay contact rating 12 Amps at 
125 VAC, 8 Amps at 250 VAC). With this optional wiring, 
on a call for humidity, the humidifier will close the 
interlock relay and energize the fan blower. The air-
proving switch must not be used if the fan interlock 
is utilized. 
All control wiring should be 22 AWG or larger 
(See figure 8). Consult with the factory if you have any 
special wiring requirements. 
Figure 7 
 
Figure 8 
 
9