3-6  Setting Up the Water Balancing Valve 
Install the plug provided in the unused water inlet on the side of the tower. Tighten and check 
for leaks. 
To prevent damage to the tower fill material, use the water throttling valve and pressure 
gauge to regulate the water pressure to the tower spray nozzle(s). The recommended 
throttling valve is a butterfly-type valve that can be locked in the correct position with a 
locknut. See Figure 6 for recommended throttling valve pressures. 
Figure 6: Throttling Valve Pressures 
Pressure 
Model 
psig 
KPa 
SF2003 10 
psig 68.95 
SF2004 7 
psig  48.26 
SF2005 3 
psig  10.68 
SF2007 5 
psig  34.47 
SF2009 6 
psig  41.37 
SF2011 8 
psig  55.16 
SF2015 10 
psig 68.95 
 
Warning!  Exceeding these pressure limits will damage the tower fill and nozzle and void 
the tower warranty. 
3-7 Initial 
Start-up 
Check for proper rotation on all fan and pump motors. Refer to the arrows atop the tower and 
on pump housings. 
Fill the system with water and adjust the float valve if you are using a float. Maintain a water 
level in the tower basin approximately one inch (25 mm) below the overflow opening. 
The tower basin acts as a sump to maintain water level. Towers using inside tanks do not 
carry water in the basin.