Sterling 882.004400.00 Manuel D’Utilisation

Page de 25
Fiberglass Cooling Towers 
Chapter 4: Operation 
Page 17 of 25 
 
Chapter 4:  Operation 
4-1  Bleed-Off and Evaporation Rates 
A proper bleed-off rate is important to limit the concentration of minerals and foreign 
materials in re-circulated water. A bleed-off equal to the evaporation rate, normally about two 
gallons per hour per ton (7.57 liters per hour per 3,780 Kcal/hr), is sufficient for many 
makeup water conditions. Refer to the suggested bleed-off arrangements in Figure 3 and 
Figure 4 on pages 14 and 14 for more information. For automatic bleed rate control, a 
conductivity controller is available through the Sales department. 
4-2  Winter Operation Considerations 
All cooling towers are subject to ice formation in sub-freezing weather. Your cooling tower 
requires a certain amount of attention and maintenance to prevent damage during these 
operating conditions. 
Follow these guidelines to reduce the chance of ice buildup: 
•  Maintain full design flow. Any reduction in water flow greatly increases the 
probability of ice forming on and around the air inlet louvers. 
•  Do not use free cooling applications during freezing weather. Reduced water 
temperatures or loading dramatically increases the chance of ice formation. Make sure 
that the leaving water temperature is set above 80ºF (27ºC) during sub-freezing 
weather so heat from the water warms the air inlet louvers and reduces ice formation 
when the fan is off. Using a thermostat to control fan cycling by leaving water 
temperature is mandatory. 
•  Do not run fans backward to thaw ice. Ice can form on the fan ring, fan guard, and 
support structures, and can severely damage fan blades. Reversed airflow can also 
blow water vapor out onto the roof and create ice fields around the cooling tower. 
•  Maintain a heat load of at least 60% of tower capacity at all times during operation in 
freezing weather. A lack of substantial load can create uneven temperatures in the 
tower and cause freezing. 
•  If you shut down your cooling tower during freezing weather, you must drain it 
completely. We recommend that you use an indoor reservoir tank to permit water to 
drain into the tank on system shutdown, whether for emergencies or actual planned 
shutdowns. 
•  An alternative is to use basin heaters if a tower basin is used as a sump. Basin heaters 
are available as an option. However, basin heaters can permit freeze-up during power 
failures if water remains in the sump. The customer is responsible for determining risk 
factors for each specific application.