Operation
12
NetworkAIR Rack Air Removal Unit Installation
Temperature Override in each Fan Speed Mode
kW mode
Exhaust temperature 
mode
Remote mode
Temp Override 
Enabled 
Fan speed will increase 
when rack equipment 
exhaust temperature 
reaches 40.5° C 
(
105° F)
No Effect
Depends on the fan speed 
selection of the remote 
device. Same as kW or 
exhaust temperature mode. 
In kW mode the 
temperature override 
setpoint can be set to 
32.2–51.6° C (90–125° 
F)
Temp Override 
Disabled 
No Effect
No Effect
No Effect
Note
If a Computer Room Air Conditioner fails, the subsequent rise in ambient temperature 
can cause the temperature override to activate. Increasing the fan speed can have an 
impact on the airflow in the room.