INSTALLATION 
VENT TERMINATION CLEARANCES: 
A)  Minimum 4-foot clearance below or beside any door or window that opens. 
B)  Minimum 1-foot clearance above any door or window that opens. 
C)  Minimum 3-foot clearance form any adjacent building. 
D)  Minimum 7-foot clearance from any grade when adjacent to public walkways. 
E)  Minimum 2-foot clearance above any grass, plants, or other combustible materials. 
F)  Minimum 3-foot clearance from an forced air intake of any appliance. 
G)  Minimum 2-foot clearance below eves or overhang. 
H)  Minimum 1-foot clearance horizontally from combustible wall. 
I)  Must be a minimum of 36-inches above the roof and 24-inches above the highest point or the roof within 10-
feet. 
FIGURE 6 
VENT TERMINATION CLEARANCES