Roberts Gorden BH30ST/EF Manuel D’Utilisation

Page de 84
B
LACKHEAT
®
  I
NSTALLATION
 O
PERATION
 
AND
 S
ERVICE
 M
ANUAL
62 of 74 
15.2.4 Automatic Flame Control Unit
Remove black ignition lead. Withdraw the connectors. 
Remove two screws from the cover. Replace if faulty. 
Refit in reverse sequence.
15.2.5 Pressure Switch
Disconnect the two silicone tubes. Remove wires from 
the three blades. Remove two screws which secure the 
pressure switch to the burner. Remove pressure switch. 
Replace pressure switch, if faulty, and refit in reverse 
sequence ensuring that the rubber tubes are reconnected 
to the switch correctly.
Note: Wires fitted as follows:
NO - Yellow
NC - White
Common - Black
15.2.6 Neons
Remove the two push on connectors and remove the 
neons by pushing downwards. Replace in reverse 
sequence.
15.3 Maintenance Checklist
Installation Code and Annual Inspections:
All installation and service of ROBERTS GORDON
®
 
equipment must be performed by a contractor 
qualified in the installation and service of equipment 
sold and supplied by Roberts-Gordon and conform 
to all requirements set forth in the ROBERTS 
GORDON
®
 manuals and all applicable 
governmental authorities pertaining to the 
installation, service and operation of the equipment. 
To help facilitate optimum performance and safety, 
Roberts-Gordon recommends that a qualified 
contractor conduct, at a minimum, annual 
inspections of your ROBERTS GORDON
®
  
equipment and perform service where necessary, 
using only replacement parts sold and supplied by 
Roberts-Gordon.
The Vicinity of the Heater
Do not store or use flammable objects, liquids or vapours near the heater. 
Immediately remove these items if they are present.
Vehicles and Other 
Objects
Maintain the clearances to combustibles. 
Do not hang anything from, or place anything on, the heater.
Make sure nothing is lodged underneath the reflector, in between the tubes 
or in the decorative or protective grilles (included with select models). 
Immediately remove objects in violation of the clearances to combustibles. 
Reflector
Support reflector with hanger and support strap.
Reflector must not touch tube.
Make sure there is no dirt, sagging, cracking or distortion.
Do not operate if there is sagging, cracking or distortion.
Make sure reflectors are correctly overlapped. 
Clean outside surface with a damp cloth.
Vent Pipe
Venting must be intact. Using a flashlight, look for obstructions, cracks on 
the pipe, gaps in the sealed areas or corrosion.
The area must be free of dirt and dust.
Remove any carbon deposits or scale using a wire brush.
Outside Air Inlet
Inlet must be intact. Look for obstructions, cracks on the pipe, gaps in the 
sealed areas or corrosion. 
The area must be free of dirt and dust. Clean and reinstall as required.