Roberts Gorden BH30UT/EF Manuel D’Utilisation

Page de 84
B
LACKHEAT
®
  I
NSTALLATION
 O
PERATION
 
AND
 S
ERVICE
 M
ANUAL
60 of 74 
the attention of the user or purchaser; instruct them in the 
safe operation of the heater(s). Advise the user that if the 
system is unflued, any reduction in the natural ventilation 
of the building may require a flue to be fitted, or additional 
ventilation grilles will be required.
14.6 ECA Approved Systems (Multiburner only)
On ECA approved systems, it must be verified that the 
requirement of 91% net combustion efficiency is met. 
Measurements of temperature and CO
2
 concentration in 
the exhaust gasses have to be done. The net combustion 
efficiency calculates as follows;
100 - [ (t
E
 - t
R
) (A/CO
2m
 - B) ] = net combustion efficiency
t
E
- Exhaust Temperature °C
t
R
- Room Temperature °C
A
- G20 = 0.37, G31 = 0.42
B
- G20 = 0.009, G31 = 0.008
CO
2m
- Measured CO
2
 Concentration %