Roberts Gorden UHD[X][S][R] 225 Manuel D’Utilisation

Page de 50
SECTION 6: V
ENTING
13
Figure 7: Separated Combustion Heater - Vertical and Horizontal Vent Termination
Figure 8: Concentric Vent Box
Vent
Termination
12" (31 cm)
Minimum from 
air inlet to vent
termination (may be 
horizontal or vertical 
clearance).
Air Intake
Termination
Vent
Air Intake*
Vertical
Option
Horizontal
Option
90°
Bend
12" (31 cm)
Minimum from wall
to vent termination.
12" (31 cm) Minimum from air inlet to 
vent termination (may be horizontal 
or vertical clearance).
Listed Thimble
through Combustible
 Wall
Vent
Air Intake
Condensate
Trap to Drain
(Optional)
NOTE: Vent supports not
 shown. Duct supports  
 not 
shown. Duct and  
 
vent supports not  
 provided by the   
 manufacturer.
12" (31 cm)
Minimum from 
wall to vent
termination. 
Model
Vent Diameter
Terminal P/N
UHD[X]S[R] 150 - 400
4" (10 cm)
90502102
Model
*Air Intake Diameter
Terminal P/N
UHD[X]S[R] 150 - 250
4" (10 cm)
90502102
UHD[X]S[R] 300 - 400
5" (13 cm)
90502105
4" (10 cm) Single
Wall Vent Pipe
(By Others)
Seal joint between single wall
and Type B vent with 
silicone sealant.
Use 3 sheetmetal 
screws equally
spaced around joint.
Use 3 sheetmetal 
screws equally
spaced around collar.
Concentric
Vent Box
6" (15 cm) Single
Wall Inlet Air Pipe
(By Others)
One piece of 4" (1
0 cm) dia, 1/4" (6 cm) 
airspace t
ype “B”
 vent.
 Selkir
k Model R
or equ
ivalent.
 (By other
s)
Combustion Air 
to Heater
Toward
Outside
Exhaust 
from Heater
4" (10 cm) or
5" (13 cm)