Roberts Gorden UHD[X][S][R] 225 Manuel D’Utilisation

Page de 50
SECTION 10: O
PERATION
 
AND
 M
AINTENANCE
23
10.2.2 Start-Up the Gas Valve (All Gases)
10.2.2.1 Check Burner Gas Pressure
1. Remove the plug in the outlet (burner) pressure 
test point and connect a pressure tap and a 
manometer.
2. With the burner firing, measure the pressure on 
the manometer. To adjust the burner pressure, 
remove the regulator cover from the valve and 
turn the regulator adjustment screw to set the 
required burner pressure as stated in the 
Technical Data Tables for the correct gas and 
model on Page 38, Section 15.2.
IMPORTANT: If the correct burner pressure cannot 
be reached, then check the inlet pressure to the 
valve with the burner firing. See Technical Data 
Tables on Page 38, Section 15.2 for inlet pressure 
requirement.
Do not continue to adjust the regulator if the 
pressure is not changing.
If the inlet pressure is too low to allow correct burner 
pressure setting, then the gas inlet pressure must be 
corrected before completing the start-up. 
Check Gas Rate
1. After burner pressure adjustment, allow the 
heater to operate for at least 15 minutes and 
then re-check settings. Adjust pressure setting 
if necessary.
2. Check gas flow rate at gas meter.
3. Turn off heater and electrical supply.
4. Remove the manometer and refit all covers to 
the valve and tighten the screw of the outlet 
pressure tap.
10.2.3 Pressure Switch
The pressure switch is factory pre-set for each 
model and is not adjustable.
10.2.4 Turning Off the Heater
Set the thermostat to the 
"
OFF
"
 position or lowest 
setting and the main burner will stop.
10.2.5 External Controls
External controls may include time switch, interlock 
switch, room thermostat and frost thermostat. 
Operate each control to ensure that they function 
correctly. Set the switches (if fitted) and 
thermostat(s) to the users’ requirements. 
10.3 Complete Start-Up
Ensure that all covers are fitted correctly and all test 
points are properly sealed.
10.3.1 Instruction to the User
Explain the controls of the heater to the user 
including how to turn it on and off, using the controls 
fitted on site. 
Give this manual to the user.
Ensure that the user is shown and understands the 
importance of maintaining clearances to 
combustibles on Page 3, Figure 1 and the user 
instructions on Page 24, Section 11 through Page 
24, Section 11.4
 and all warnings defined in this 
manual.