Roberts Gorden UHD[X][S][R] 225 Manuel D’Utilisation

Page de 50
SECTION 14: R
EPLACEMENT
 P
ARTS
33
14.2 Burner Compartment
14.2.1 Burner Injectors
MODEL
UHD[X][S][R]
150
UHD[X][S][R]
175
UHD[X][S][R]
200
UHD[X][S][R]
225
UHD[X][S][R]
250
UHD[X][S][R]
300
UHD[X][S][R]
350
UHD[X][S][R]
400
Orifice 
Quantity
7
8
9
10
11
12
14
14
Natural Gas (G20)
Orifice 
Marking
43
43
2.25 mm
2.25 mm
2.25 mm
40
40
40
P/N
91930043
91930043
91930225
91930225
91930225
91930040
91930040
91930040
Propane (G31)
Orifice 
Marking
1.35 mm
1.35 mm
54
54
54
1.45 mm
53
53
P/N
91930135
91930135
91930054
91930054
91930054
91930145
91930053
91930053
Remove flexible
air duct from spigot 
Remove
access plate
Remove screws and
pull off burner 
compartment cover
Viewing port
for flame probe 
Viewing port
for ignition electrode 
Flame Probe 
Burner
Compartment
Cover 
Rubber Seal
Ignition Electrode 
The burner compartment is 
a sealed compartment. 
Following any work, 
re-seal the compartment 
with the gas pipe rubber 
seal fully in place and all 
screws fitted and tight.
NOTE: Separated combustion 
            model shown. 
Remove manifold
screws and pull
out manifold
Manifold
Inshot
Burners
Injectors
Burner
Screws
Burner
venturi
Unscrew
Orfices
Manifold
Marking
Folded 
Hem
Ensure gas tight fitting of injectors.
Ensure correct alignment with burners.