UHD[X][S][R] heaters have automatic ignition 
burners for ON/OFF operation only.
3.2 Manufactured Units
Gas-fired, power-vented duct furnace with tubular 
heat exchanger. Units shall have a minimum of 82% 
thermal efficiency. The standard unit shall consist of 
a non-separated combustion design with an 
aluminized heat exchanger. Design and heat 
exchanger alternatives shall be offered as follows:
•  Separated Combustion: A separated 
combustion unit shall feature an enclosed, 
sealed burner box. A piece of flexible air duct 
connects this burner box to a flange on the 
cabinet. Combustion air should be ducted from 
outside the heated space, with the ductwork 
connecting to the unit with the use of the flange.
•  Stainless Steel Heat Exchanger: A stainless 
steel heat exchanger unit shall consist of heat 
exchanger tubes, heat exchanger tube supports, 
heat exchanger tube plates and vent box 
produced of 409 stainless steel.
3.3 Location and Suspension
All models:
• Must be installed indoors.
• Must be installed on the positive pressure side of 
the air circulation blower.
• Must be installed in a level position with 
horizontal discharge.
• May be mounted on a shelf of non-combustible 
material.
• May be suspended from above (See Page 8, 
Figure 3) or from wall brackets of sufficient 
strength to support the heater as listed in the 
Dimension Data Table on Page 37, Section 15.1
• Must be installed in a manner which allows 
access to all serviceable components.
See Page 3, Figure 1 for details.
3.4 Minimum Required Installation Clearances
Clearances around the heater and vent must be as 
indicated on Page 3, Figure 1 and Page 11, Figure 4 
through Page 14, Figure 9 to ensure access for 
servicing, and correct operation.
3.5 Clearances to Combustibles
Clearances must be as indicated on Page 3, Figure 
1
. If clearances to combustibles are not indicated, 
then installation clearances apply.
Figure 1: Clearances to Combustibles
WARNING
Fire Hazard
Some objects can catch fire or explode 
when placed close to heater.
Keep all flammable objects, liquids and 
vapors the required clearances to 
combustibles away from heater.
Failure to follow these instructions can 
result in death, injury or property damage.
6"
(15 cm)
6"
(15 cm)
31"*
(79 cm)
6"
(15 cm)
Clearance to Vent: 2" (5 cm)
*31" (79 cm) minimum is necessary 
for servicing.