Beckett AFII 150 Manuel D’Utilisation

Page de 16
Page 6
 
RWB 6104 BAFII R01
Inspect/Prepare Installation Site
Inspect Chimney or Direct Vent System
  Inspect the chimney or vent. Make sure it is properly 
sized and in good working condition. Follow the in-
structions supplied by the appliance manufacturer.
Combustion Air Supply Information
  See NFPA Standard 31 for complete details.
  Appliances located in confi ned  spaces:  All 
confi ned spaces should have two (2) permanent 
openings; one near the top of the enclosure and 
one near the bottom of the enclosure. Each open-
ing must have a free area of not less than one (1) 
square inch per 1,000 BTU’s per hour of the total 
input rating of all appliances within the enclosure. 
The openings should have free access to the build-
ing interior, which should have adequate infi ltration 
from the outside.
  Exhaust fans and other air-using devices: Size 
air openings large enough to supply all air-using 
devices in addition to the minimum size required 
for combustion air. If there is any possibility of the 
equipment room developing a negative pressure 
due to exhaust fans, clothes dryers, etc., either 
pipe combustion air directly to the burner or provide 
a sealed enclosure for the burner and supply it with 
its own combustion air supply.
Direct/Sidewall Venting Application 
·  When sidewall venting appliances, carefully follow 
appliance and power venter instructions for instal-
lation and wiring.
·  AFII burners are equipped with a removable air in-
let to allow use of a 4” duct to supply outside air 
for combustion. Do not exceed 70 equivalent feet.  
Allow 6 feet for each elbow.
1. Remove the inlet cover.
2. Insert 4” duct into the inlet ring.  
3. Fasten duct into place using at least 3 sheet met-
al screws evenly spaced around the inlet ring. 
Refer to Figure 2.
4. Remove the barometric draft control unless it is 
in the same atmospheric pressure zone as the 
inlet.
  On the outside of the home use a 90° elbow pointed 
downward with a 
1/4
” mesh screen over its opening.  
The air inlet elbow must be located above the snow 
line and in such a way as to prevent leaves and/or 
other debris from blocking the air fl ow.  Such debris 
will prevent proper operation of the burner.  Refer to 
local codes for proper location of inlet.
The burner cannot properly burn the fuel if it is not 
supplied with a reliable combustion air source.
Follow the guidelines in the latest editions of the 
NFPA 31 and CSA-B139 regarding providing ad-
equate air for combustion and ventilation.
Failure to provide adequate air supply could se-
riously affect the burner performance and result 
in damage to the equipment, asphyxiation, ex-
plosion or fi re hazards.
Adequate Combustion 
and Ventilation Air Supply 
Required
WARNING
!
Figure 2. Outside Air Connection
4 inch Duct
Air
Inlet
Elbow
1/4”
Mesh
Screen
Inlet Ring
SK8810
Figure 1. Burner label location
SK9642
SK9642