Beckett CF1000 Manuel D’Utilisation

Page de 20
Form 6104 BCF10-R06
17
Maintenance and Service
Do not tamper with the burner or controls or make 
any adjustments unless you are a trained and qualifi ed 
service technician.
To ensure continued reliable operation, a qualifi ed 
service technician must service this burner annually.
More frequent service intervals may be required in dusty 
or adverse environments.
Operation and adjustment of the burner requires technical 
training and skillful use of combustion test instruments 
and other test equipment.
y
y
y
y
Tampering with or making incorrect 
adjustments could lead to equipment 
malfunction and result in asphyxia-
tion, explosion or fi re.
Annual Professional 
Service Required
Annual service 
— by qualifi ed service techni-
cian
Have the burner inspected, tested and started at least annually 
by a qualifi ed service technician. This annual test/inspection 
should include at least the following:
Replace the oil supply line fi lter. The line fi lter cartridge 
must be replaced to avoid contamination of the fuel unit 
and nozzle.
Inspect the oil supply system. All fi ttings should be leak-
tight. The supply lines should be free of water, sludge and 
other restrictions.
Remove and clean the pump strainer if applicable.
Replace the nozzle with the exact brand, pattern, gph, fl ow 
rate and spray angle.
Clean and inspect the electrodes for damage, replacing any 
that are cracked or chipped.
Check electrode tip settings. Replace electrodes if tips are 
rounded.
ˆ
ˆ
ˆ
ˆ
ˆ
ˆ
Inspect the igniter spring contacts.
Clean the cad cell lens surface, if necessary.
Inspect all gaskets. Replace any that are damaged or would 
fail to seal adequately.
Inspect the combustion head and air tube. Remove any car-
bon or foreign matter. Replace all damaged units with exact 
parts.
Clean the blower wheel, air inlet, air guide, and burner 
housing of any lint or foreign material.
If motor is not permanently lubricated, oil motor with a few 
drops of SAE 20 nondetergent oil at each oil hole. DO NOT 
over oil motor. Excessive oiling can cause motor failure.
Check motor current. The amp draw should not exceed the 
nameplate rating.
Check all wiring for secure connections or insulation 
breaks.
Check the pump pressure and cutoff function.
Check primary control safety lockout timing.
Check ignition system for proper operation.
Inspect the vent system and chimney for soot accumulation 
or other restriction.
Clean the appliance thoroughly according to the manufac-
turer’s recommendations.
Check the burner performance. Refer to the section “Set 
combustion with test instruments”.
It is good practice to make a record of the service performed 
and the combustion test results.
Monthly maintenance
 — by owner
Observe combustion air openings and vent system for 
integrity. Openings must be clean and free of obstructions.
Check oil lines and fi ttings to verify there are no leaks.
Observe burner ignition and performance to verify smooth 
operation.
Shut the system down if you observe abnormal or 
questionable operation. Call a qualifi ed service agency for 
professional inspection and service.
ˆ
ˆ
ˆ
ˆ
ˆ
ˆ
ˆ
ˆ
ˆ
ˆ
ˆ
ˆ
ˆ
ˆ
ˆ
‰
‰
‰
‰