Beckett CF500 Manuel D’Utilisation

Page de 16
6104 BCF5 R07
11
Keep Service Access 
Covers Securely Installed
These covers must be securely in place to 
prevent electrical shock, damage from exter-
nal elements, and protect against injury from 
moving parts.  
All covers or service access plates must be in place at 
all times except during maintenance and service. 
This applies to all controls, panels, enclosures, switch-
es, and guards or any component with a cover as part 
of its design.  
y
y
Safety controls are designed and installed to provide 
protection.
Do not tamper with, or bypass any safety control.
If a safety control is not functioning properly, shut off 
all main electrical power and fuel supply to the burner 
and call a qualifi ed service agency immediately.
y
y
y
Tampering with, or bypassing safety controls 
could lead to equipment malfunction and result  
in asphyxiation, explosion or fi re. 
Do Not Bypass Safety 
Controls
Prepare the burner for start-up
This burner must be installed and prepared for start-up 
by a qualifi ed service technician who is trained and ex-
perienced in commercial oil burner system installation 
and operation.
Do not attempt to start the burner unless you are fully 
qualifi ed.
Do not continue with this procedure until all items in 
the “Prepare the burner for start-up” section have been 
verifi ed.  
Carefully follow the wiring diagrams, control instruc-
tion sheets, fl ame safeguard sequence of operation, test 
procedures and all appliance manufacturer’s directions 
that pertain to this installation.
If any of these items are not clear or are unavailable, 
call Beckett at 1-800-645-2876 for assistance.
y
y
y
y
y
Incorrect installation and mishandling of start-
up could lead to equipment malfunction and re-
sult in asphyxiation, explosion or fi re.
Professional Installation 
and Service Required
Oil nozzle has been selected correctly and securely 
installed in the nozzle adapter.
Fuel unit by-pass plug has not been installed for one-
pipe oil system.  
 
 
 
 
 
 
 
 
 
 
By-pass plug has been installed for two-pipe oil 
system.
Fuel connection to nozzle line assembly is secure.
Dimension Z has been set per the ‘Set Z Dimension’ 
instructions detailed earlier in this manual.  The acorn nut 
(Figure 7, item C) should never be loosened once the Z 
dimension is initially set.
Fuel supply line is correctly installed, the oil tank is 
suffi ciently fi lled, and shut-off valves are open.
Burner is securely mounted in appliance, with pressure 
fi ring plate and gasket installed for pressurized chamber 
application.
Appliance has been fi lled with water (boilers) and controls 
have been operationally checked.
Burner has been installed in accordance with appliance 
manufacturer’s instructions (when available).
Also refer to appliance manufacturer’s instructions (when 
available) for start-up procedures.
Initial head position (Figure 7)
The indicator plate assembly markings correspond to head 
position settings. 
Loosen the fastener (Figure 7, item d)  and slide the 
indicator plate until the number on the indicator plate 
corresponds to the initial head setting listed in Table 4, for 
the desired fi ring rate.
When the head position has been set, tighten the fastener 
and the spline nut.
‰
‰
‰
‰
‰
‰
‰
‰
‰
‰
‰
y
y
y
Start-up checklist - Verify the following before 
attempting to start burner.
Combustion air supply and venting have been inspected 
and verifi ed to be free of obstructions and installed in 
accordance with all applicable codes.
‰
Table 4 - Initial indicator adjustment plate settings 
(head position)
Rate GPH
Approximate head settings
CF500
CF800
Tube A
Tube B
1.75
0
--
--
2.25
0
3.00
4
0
--
3.50
5
1
--
4.00
5
2
--
5.00
6
4
3
5.50
6
4
4
6.00
--
4
4
7.00
--
6
5
8.00
--
--
6