Heat Controller BHD-651-G Manuel D’Utilisation

Page de 17
Heat Controller, Inc. 
Portable Dehumidifier with R-410A 
BHD-G Service Manual
14
Complaint
Cause
Remedy
Fan motor noise
Fan
Replace the fan if cracked, out of balance, or partially 
missing.
Blower
Replace the blower if cracked, out of balance, or partially 
missing.
Loose screws
Tighten them.
Worn bearings
Replace the motor if knocking sounds continues when 
running, or if the motor hums or noise appears to be internal 
while running.
Compressor fan motor runs 
only
Voltage
Check voltage. Call an electrician if not within limits.
Wiring
Check the wire connections, if loose, repair or replace 
the terminal. If wires are off, refer to wiring diagram for 
identification, and replace. Check wire locations. If not per 
wiring diagram, correct.
Main PCB failure
Replace the main PCB.
Capacitor (Discharge 
capacitor before testing)
Check the capacitor. Replace if not within 10% of 
manufacturer’s rating. Replace if shorted, open, or damaged.
Humidity sensor
Replace if shorted, open, or damaged.
Compressor
Check the compressor for open circuit or ground. If open or 
grounded, replace the compressor.
Insufficient capacity
Air filter
Clean if restricted.
Condenser and 
Evaporator
Clean if restricted.
Fan motor
Check the fan capacitor and replace if not within 10% of 
manufacturer’s rating.
Room structure
Ensure that the room the unit is operating in is sealed well. 
Close any open doors or windows.
Air flow
Clean or remove any barrier that blocks the inlet/outlet air 
flow of the unit.
Less refrigerant
Check the lines for leakage. Recycle the refrigerant, correct 
the leakage points and recharge.
Capillary tube
Regulate the flow of capillary tube and make the evaporating 
temperature appropriate if the evaporator is frosted.
Compressor
The inlet and outlet valve of the compressor is damaged, 
making the low pressure connected with the high pressure. 
The refrigerating system is difficult to produce high pressure 
and low pressure. Replace the compressor after checking 
for the failure.
The compressor does not stop 
even if the room humidity has 
reached the set RH%.
Humidity sensor
Check and replace if the Humidity sensor, if open or 
damaged.
Main PCB
Check and replace the main PCB 
The unit starts and stops 
frequently.
Power supply
The input power supply voltage is too low. Call an electrician 
if not within limits.
Humidity sensor
Check and replace if the Humidity sensor, if open or 
damaged.
Main PCB
Check and replace the main PCB.