Emerson 210-2000 Manuel D’Utilisation

Page de 4
             
 
 
 
Carbon Dioxide Sensor 
Product Information Sheet
 
210-2000
 
Overview 
CPC’s CO
2
 sensor (P/N 210-2000) is a non-dispersive 
infrared analyzer designed for measuring 
environmental CO
2
 concentration in ventilation 
systems and indoor spaces. Its measurement range of 
0-2000 or 0-5000 ppm covers the range required to 
monitor compliance with ASHRAE and other 
ventilation efficiency standards. 
 
An LCD display is available to provide local indication 
of CO
2
 concentration and facilitate the setup and 
calibration process. An adjustable setpoint relay is 
available for direct control and alarm applications. 
Microprocessor-based digital electronics and a 
unique self-calibration algorithm improves long-term 
stability and accuracy 
  
Mounting 
Before mounting, remove the door from the circuit 
board by pressing a screwdriver against the locking 
tab on the top of the enclosure. Pry the circuit board 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
away from the mounting plate using a screwdriver 
inserted into the two tab slots on the top of the 
enclosure. 
 
Choose a location for the sensor with good air 
circulation, away from ventilation inlets, doors, 
windows, or other points where fresh air enters the 
room. The sensor should be mounted at least 4-1/2 
feet above the floor. The environment temperature 
must be within 32°–112°F (0°–50°C). 
 
If wiring will be coming in through the mounting 
plate from the back, punch out openings in the 
mounting plate and use the plate as a template for 
locating holes. Mount the mounting plate against a 
wall or other flat surface by using the two mounting 
holes and the screws provided (use wall anchors for 
drywall installations). 
 
NOTE:  Sensors must be mounted vertically (straight 
up and down) to ensure proper readings. 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 1 - CO
2
 Sensor (exploded view) 
Carbon Dioxide Sensor 
Product Information Sheet
 
40