AIR FOR COMBUSTION 
AND VENTILATION
 WARNING: This heater shall 
not  be  installed  in  a  confined 
space or unusually tight construc-
tion unless provisions are provid-
ed for adequate combustion and 
ventilation air. Read the following 
instructions to insure proper fresh 
air for this and other fuel-burning 
appliances in your home. 
Todayʼs homes are built more energy efficient 
than ever. New materials, increased insulation, and 
new construction methods help reduce heat loss 
in homes. Home owners weather strip and caulk 
around windows and doors to keep the cold air out 
and the warm air in. During heating months, home 
owners want their homes as airtight as possible.
While it is good to make your home energy effi-
cient, your home needs to breathe. Fresh air must 
enter your home. All fuel-burning appliances need 
fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and fuel 
burning appliances draw air from the house to 
operate. You must provide adequate fresh air for 
these appliances. This will insure proper venting 
of vented fuel-burning appliances.
PROVIDING ADEQUATE 
VENTILATION 
The following are excerpts from National Fuel 
Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, 
Air for Combustion and Ventilation.
All spaces in homes fall into one of the three fol-
lowing ventilation classifications:
1.  Unusually Tight Construction
2.  Unconfined Space
3.  Confined Space
The information on pages 6 through 8 will help you clas-
sify your space and provide adequate ventilation. 
Unusually Tight Construction
The air that leaks around doors and windows may 
provide enough fresh air for combustion and ven-
tilation. However, in buildings of unusually tight 
construction, you must provide additional fresh air.
Unusually tight construction is defined as 
construction where:
a.  walls and ceilings exposed to the out-
side  atmosphere  have  a  continuous 
water  vapor  retarder  with  a  rating  of 
one perm (6 x 10
-11 
kg per pa-sec-m
2
) or 
less with openings gasketed or sealed 
and 
b.  weather stripping has been added on 
openable windows and doors and 
c.  caulking  or  sealants  are  applied  to 
areas  such  as  joints  around  window 
and door frames, between sole plates 
and floors, between wall-ceiling joints, 
between  wall  panels,  at  penetrations 
for plumbing, electrical, and gas lines, 
and at other openings.  
If your home meets all of the three criteria 
above, you must provide additional fresh 
air.  See  Ventilation  Air  From  Outdoors

page 6. 
If  your  home  does  not  meet  all  of  the 
three  criteria  above,  proceed  to  Deter-
mining  Fresh-Air  Flow  for  Fireplace 
Location
, below. 
Confined Space and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1/NFPA 
54  defines  a  confined  space  as  a  space  whose 
volume is less than 50 cubic feet per 1,000 Btu 
per hour (4.8 m
3
 per kw) of the aggregate input 
rating of all appliances installed in that space and 
an unconfined space as a space whose volume is 
not less than 50 cubic feet per 1,000 Btu per hour 
(4.8 m
3
 per kw) of the aggregate input rating of 
all appliances installed in that space. Rooms com-
municating directly with the space in which the 
appliances are installed*, through openings not 
furnished with doors, are considered a part of the 
unconfined space.
* Adjoining  rooms  are  communicating  only  if 
there are doorless passageways or ventilation grills 
between them.
DETERMINING FRESH-AIR FLOW 
FOR HEATER LOCATION
Determining if You Have a Confined or 
Unconfined Space
Use this work sheet to determine if you have a 
confined or unconfined space.
Space: 
Includes the room in which you will install 
fireplace plus any adjoining rooms with doorless pas-
sageways or ventilation grills between the rooms.
1.  Determine the volume of the space (length x 
width x height).
 
Length x Width x Height =__________cu. ft. 
(volume of space)
 
Example: 
Space  size  20  ft.  (length)  x  16  ft. 
(width) x 8 ft. (ceiling height) = 2560 cu. ft. 
(volume of space)