Regency B36X Manuel D’Utilisation

Page de 64
33
Regency Bellavista™ B36X Gas Fireplace
on top and bottom. Fasten the other thimble 
half to the inside wall. The thimble halves slip 
inside each other and can be adjusted for 2 
x 4 or 2 x 6 walls. 
5)  Slip the assembled liner and termination 
assembly through the thimble making sure 
the termination cap faces up (there are 
markings on the cap that show which way 
is up). This will position the termination cap 
with proper down slope for draining water. 
Fasten the cap to the outer wall with the 4 
supplied screws. 
6)  Pull the centre 5"(127mm) liner and outer 
 
8"(203mm) liner out enough to slip over the 
fl ue collars of the fi replace.  (You may wish to 
cut the liner shorter to make it more workable.) 
Do not bend liner more than 90
o
The liners 
must slip over the collars a minimum of 
1-3/8".
7)  Apply Mill Pac over the fi replace inner collar 
and slip the 5"(127mm) liner down over it and 
attach with 3 supplied screws.
8)  Do the same with the 8"(203mm) liner.
9)  Apply a bead of silicone between the thimble 
and termination and around the outer edge 
of the terminal at the wall in order to keep 
the water out.
IMPORTANT: Do not locate termination 
hood where excessive snow or ice 
buildup may occur. Be sure to check vent 
termination area after snow falls, and clear 
to prevent accidental blockage of venting 
system. When using snow blowers, make 
sure snow is not directed towards vent 
termination area.
UNIT INSTALLATION
HORIZONTAL TERMINATION
WITH 5" X  8" FLEX VENT SYSTEM
Note:  5" x 8" venting is limited to vent 
          confi gurations found on page 17 of this      
          manual.
Note:  A top clearance of 2"(51mm) and side 
& bottom clearance of 1-1/2"(38mm) 
must be maintained; except when 
passing through a wall, ceiling, or at 
the termination where the use of a 
fi restop or wall thimble reduces the 
required clearance to 1-1/2" (38mm). 
We recommend framing a 11"(279mm) 
x 11"(279mm) (inside dimensions) 
hole to give structural rigidity for 
mounting the termination.
1)  Locate the unit in the framing, rough in the 
gas (preferably on the right side of the unit). 
Locate the centerline of the termination and 
mark wall accordingly. Cut an 11"(279mm) 
hole in the wall (inside dimension).
Note:  If installing termination on a siding 
covered wall,  a vinyl siding standoff 
or vinyl furring strips must be used 
to ensure that the termination is not 
recessed into the siding.
2) Level the fi replace and fasten it to the fram-
ing using nails or screws through the nailing 
strips.
3)  Assemble the vent assembly by applying 
Mill Pac to the 5"(127mm) inner collar of the 
termination and  slipping the 5"(127mm) liner 
over it at least 1-3/8" (35mm). Fasten with 
the 3 screws (drilling pilot holes will make this 
easier). Apply Mill Pac or high temperature 
silicone to the 8"(203mm) fl ex pipe and slip 
it over the 8" outer collar of the vent terminal 
at least 1-3/8"(35mm) and fasten with the 3 
screws.
NOTE:   Horizontal sections must be sup-
ported at intervals not exceeding 3 
feet (0.9 meter). (Flame picture and 
performance will be affected by sags 
in the liner).
4)  Separate the 2 halves of the wall thimble and 
securely fasten the one with the tabs to the 
outside wall making sure that the tabs are 
AstroCap XL
Termination Cap
2” x 4” or 2” x 6”
8" dia.
air intake
5” dia. flue pipe
with spring spacer
Screws
Screws
Wall Thimble
Vinyl Siding
ASTROCAPXL
DIMENSIONS (946-623/P)
INSTALLATION